Heat pump reverse cycle heating capacity

Operation

Table 23. Heating total wattage input — heat pumps

 

 

PTHE

PTHE

PTHE

PTHE

PTHE

PTHE

PTHE

PTHE

Outside air

Room air

0701

0702

0901

0902

1201

1202

1501

1502

dry-bulb

dry-bulb

Min

Max

Min

Max

Min

Max

Min

Max

 

 

 

 

 

 

 

 

 

 

 

 

520

535

670

685

940

965

1210

1235

 

85

580

620

745

790

1030

1115

1295

1435

 

 

 

 

 

 

 

 

 

 

 

80

565

600

725

775

1010

1095

1275

1410

50

 

 

 

 

 

 

 

 

 

75

550

590

710

760

990

1075

1245

1385

 

 

 

 

 

 

 

 

 

 

 

70

535

575

695

740

970

1050

1225

1360

 

 

 

 

 

 

 

 

 

 

 

65

520

560

675

720

945

1025

1200

1335

 

 

 

 

 

 

 

 

 

 

 

85

565

600

710

760

1000

1080

1240

1375

 

 

 

 

 

 

 

 

 

 

 

80

550

590

695

740

975

1060

1214

1355

45

 

 

 

 

 

 

 

 

 

75

630

570

680

730

955

1040

1190

1330

 

 

 

 

 

 

 

 

 

 

 

70

515

555

660

710

930

1010

1160

1305

 

 

 

 

 

 

 

 

 

 

 

65

500

540

640

690

910

995

1145

1280

 

 

 

 

 

 

 

 

 

 

 

85

545

580

680

725

950

1040

1185

1320

 

 

 

 

 

 

 

 

 

 

 

80

530

570

660

710

940

1020

1160

1300

40

 

 

 

 

 

 

 

 

 

75

515

555

640

690

920

1000

1135

1270

 

 

 

 

 

 

 

 

 

 

 

70

500

535

630

675

895

980

1110

1250

 

 

 

 

 

 

 

 

 

 

 

65

480

520

610

675

875

955

1090

1220

 

 

 

 

 

 

 

 

 

 

 

85

525

565

650

695

925

1010

1130

1270

 

 

 

 

 

 

 

 

 

 

 

80

510

550

630

675

900

985

1110

1240

35

 

 

 

 

 

 

 

 

 

75

500

535

610

655

880

965

1080

1220

 

 

 

 

 

 

 

 

 

 

 

70

480

520

600

645

855

940

1060

1190

 

 

 

 

 

 

 

 

 

 

 

65

465

500

580

625

940

922

1030

1265

 

 

 

 

 

 

 

 

 

 

Notes: Shaded area is rating wattage

Table 24.

Heat pump reverse cycle heating capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PTEE07

 

 

PTEE09

 

 

PTEE12

 

 

PTEE15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

 

208

230

265

208

230

265

208

230

265

208

230

265

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Amps

 

2.5

2.4

2.4

3.4

3.2

2.6

4.3

4.0

3.5

5.7

5.3

4.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Btu/H

 

6400

6600

6600

7600

7800

8000

10100

10300

10300

12800

13100

13100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COP

 

3.6

3.6

3.6

3.2

3.2

3.4

3.3

3.3

3.3

3.0

3.0

3.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cfm (dry)

 

220

230

250

240

270

270

330

360

350

350

390

380

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

Btu/H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor

62

7200

7400

7400

9600

9700

9700

12800

13000

13000

15700

15800

15800

Ambient

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

6900

7100

7100

9300

9600

9600

12500

12800

12800

15000

15200

15200

 

52

6500

6700

6700

8700

9000

9000

11700

12000

12000

14200

14400

14400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rating

47

6200

6400

6400

8200

8400

8400

10900

11200

11200

13300

13500

13500

Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

42

5900

6100

6100

7700

7900

7900

10200

10500

10500

12500

12700

12700

 

37

5600

5800

5800

7200

7400

7400

9500

9700

9700

11700

11900

11900

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

5300

5500

5500

6700

6900

6900

9600

8900

8900

10800

11000

11000

 

27

5000

5200

5200

6200

6300

6300

7900

8200

8200

10000

10200

10200

 

24

4800

5000

5000

5800

6000

6000

7500

7800

7800

9500

9700

9700

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PTAC-SVX01C-EN

27

Page 27
Image 27
Trane PTAC-SVX01C-EN manual Operation, Table, Heat pump reverse cycle heating capacity