Trane TWA075A, TWE200B, TWA200B Performance, DataSystem, Table PD-9- Gross Heating Capacities MBh

Models: TWA200B TWA075A TWE200B TWE050A

1 56
Download 56 pages 34.19 Kb
Page 20
Image 20
Table PD-9 — Gross Heating Capacities (MBh)

Performance

Data(System)

Table PD-9 — Gross Heating Capacities (MBh)

TWA075A Heat Pump with TWE075A Air Handler At 2500 CFM (I-P)

Outdoor

Heating Capacity (Btu/1000) At

 

Total Power in Kilowatts At

 

Temperature

Indicated Indoor Dry BulbTemperature

Indicated Indoor Dry BulbTemperature

(°F)

60

70

75

80

60

70

75

80

-18

33.0

28.7

27.1

25.9

5.6

5.7

5.9

6.0

-13

34.1

30.4

29.0

27.9

5.5

5.7

5.9

6.1

-8

35.6

32.4

31.2

30.3

5.5

5.8

5.9

6.2

-3

37.5

34.8

33.9

33.2

5.5

5.8

6.0

6.3

2

40.0

37.7

37.0

36.4

5.5

5.9

6.1

6.4

7

42.8

41.1

40.5

40.1

5.6

6.0

6.2

6.5

12

46.2

44.9

44.4

44.2

5.6

6.1

6.3

6.6

17

50.0

49.1

48.7

48.5

5.7

6.2

6.5

6.8

22

54.4

53.6

53.4

53.2

5.8

6.3

6.6

7.0

27

59.2

58.6

58.4

58.2

5.9

6.4

6.8

7.1

32

64.5

63.9

63.7

63.5

6.0

6.6

6.9

7.3

37

69.9

69.4

69.1

68.8

6.1

6.7

7.1

7.5

42

75.7

75.1

74.7

74.3

6.2

6.9

7.2

7.6

47

81.8

81.1

80.6

80.1

6.4

7.0

7.4

7.8

52

88.3

87.4

86.8

86.2

6.5

7.2

7.6

8.0

57

95.1

93.9

93.2

92.4

6.7

7.4

7.7

8.1

62

102.0

100.6

99.8

98.9

6.8

7.5

7.9

8.3

67

109.0

107.4

106.5

105.5

7.0

7.7

8.1

8.5

72

116.3

114.5

113.4

112.3

7.2

7.9

8.2

8.6

Table PD-9 — Gross Heating Capacities (kW)

TWA075A Heat Pump with TWE075A Air Handler At 4247 m3/h (SI)

Outdoor

 

Heating Capacity (kW) At

 

 

Total Power in Kilowatts At

 

Temperature

Indicated Indoor Dry BulbTemperature

Indicated Indoor Dry BulbTemperature

(°C)

15.6

21.1

23.9

26.7

15.6

21.1

23.9

26.7

-27.8

9.7

8.4

7.9

7.6

5.5

6.0

6.2

6.5

-25.0

10.0

8.9

8.5

8.2

5.6

6.1

6.3

6.6

-22.2

10.4

9.5

9.1

8.9

5.7

6.2

6.5

6.7

-19.4

11.0

10.2

9.9

9.7

5.8

6.3

6.6

6.9

-16.7

11.7

11.0

10.8

10.7

5.9

6.5

6.7

7.0

-13.9

12.5

12.0

11.9

11.7

6.0

6.6

6.9

7.2

-11.1

13.5

13.1

13.0

12.9

6.2

6.7

7.0

7.4

-8.3

14.7

14.4

14.3

14.2

6.3

6.9

7.2

7.5

-5.6

15.9

15.7

15.6

15.6

6.5

7.0

7.4

7.7

-2.8

17.3

17.2

17.1

17.0

6.6

7.2

7.5

7.9

0.0

18.9

18.7

18.7

18.6

6.8

7.4

7.7

8.1

2.8

20.5

20.3

20.2

20.1

6.9

7.6

7.9

8.3

5.6

22.2

22.0

21.9

21.8

7.1

7.8

8.1

8.5

8.3

24.0

23.7

23.6

23.4

7.3

8.0

8.4

8.8

11.1

25.9

25.6

25.4

25.2

7.5

8.2

8.6

9.0

13.9

27.8

27.5

27.3

27.1

7.7

8.4

8.8

9.2

16.7

29.9

29.5

29.2

29.0

7.9

8.7

9.1

9.5

19.4

31.9

31.5

31.2

30.9

8.1

8.9

9.3

9.8

22.2

34.1

33.5

33.2

32.9

8.4

9.2

9.6

10.0

Correction Factors - Other Airflows

 

Airflow = 2500 cfm (4247 m3/h)

(Table Value x Correction Factor = Value at new airflow)

Heating Capacity (High Temp.) = 81,000 (23.72)

 

 

 

Heating Capacity (Low Temp.) = 49,000 (14.35)

Airflow

2250 cfm

2750 cfm

Compressor Power (High Temp) = 5.67 kW

 

3822 m3/h

4672 m3/h

Compressor Power (Low Temp) = 4.80 kW

Heating Capacity

x0.99

x1.01

Coeff. Of Perf. (High Temp) = 3.4

Compressor kW

x1.02

x0.98

Coeff. Of Perf. (Low Temp) = 2.3

 

 

 

Outdoor Fan Power = 550 watts

Values at ARI Rating Conditions of:

 

Indoor Fan Power = 800 watts

70F (21.1C) and 47/43F (8.3/6.1C)(High Temp.Cond.)

 

70F (21.1C) and 17/15F (-8.3/-9.4C)(Low Temp. Cond)

Note:

 

 

 

1. Rated with 25 feet of 1-3/8" suction and 1/2" liquid line.

20

SSP-PRC002-EN

Page 20
Image 20
Trane TWA075A Performance, DataSystem, Table PD-9- Gross Heating Capacities MBh, Table PD-9- Gross Heating Capacities kW