Table PD-15— Continued

Performance

 

Data

(Air Handler)

Table PD-15 — Evaporator Fan Performance TWE075A (I-P)

 

 

 

 

 

 

 

External Static Pressure (In. Of Water Column)

 

 

 

 

 

 

 

 

 

 

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1.10

 

CFM

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2000

443

0.44

489

0.49

535

0.54

581

0.59

627

0.64

673

0.69

719

0.74

765

0.79

791

0.83

818

0.89

 

2125

453

0.46

499

0.52

546

0.57

592

0.63

638

0.68

684

0.74

730

0.79

771

0.85

798

0.90

825

0.96

 

2250

463

0.49

510

0.55

556

0.61

602

0.67

649

0.73

695

0.79

742

0.85

776

0.91

804

0.97

831

1.03

 

2375

473

0.51

520

0.57

567

0.64

613

0.70

660

0.77

706

0.83

753

0.90

782

0.97

810

1.03

838

1.10

 

2500

445

0.47

489

0.54

533

0.60

578

0.67

622

0.73

667

0.80

711

0.86

756

0.93

784

0.99

813

1.07

842

1.14

 

2625

464

0.50

506

0.57

548

0.63

589

0.69

631

0.76

672

0.82

714

0.88

757

0.95

786

1.01

815

1.09

844

1.17

 

2750

484

0.53

523

0.59

562

0.66

601

0.72

640

0.78

678

0.84

717

0.91

758

0.97

787

1.03

817

1.12

847

1.21

 

2875

504

0.56

540

0.62

576

0.68

612

0.74

648

0.81

684

0.87

720

0.93

759

0.99

789

1.05

819

1.15

850

1.24

 

3000

524

0.59

557

0.65

590

0.71

624

0.77

657

0.83

690

0.89

723

0.95

760

1.01

790

1.07

821

1.17

853

1.27

 

 

1.0 HP Standard Motor

 

 

 

 

1.0 HP Standard Motor

 

 

 

 

1.5 HP Oversized

Motor

 

and Low Static Drive

 

 

 

 

 

andDrive

 

 

 

 

 

and High Static Drive

Notes:

1.Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.

2.Tabulated brake horsepower is the motor shaft output required.

3.Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.

Table PD-15— Continued

 

External Static Pressure (In. Of Water Column)

 

1.20

1.30

1.40

1.50

1.60

CFM

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2000 844 0.96 871 1.02 897 1.09 924 1.15 950 1.21

2125 852 1.03 879 1.09 906 1.16 933 1.22 — —

2250 859 1.10 886 1.17 914 1.23 942 1.30 — —

2375 866 1.17 894 1.24 922 1.30 950 1.37 — —

2500 870 1.21 899 1.29 928 1.36 — — — —

2625 874 1.25 903 1.33 932 1.42 — — — —

2750 877 1.29 907 1.38 937 1.47 — — — —

2875 880 1.33 911 1.43 942 1.52 — — — —

3000 884 1.37 915 1.48 946 1.58 — — — —

1.5HP Oversized Motor and High Static Drive

1.0HP Standard Motor

andDrive

Table PD-15 — Evaporator Fan Performance TWE075A (SI)

 

 

 

 

 

 

 

 

External Static Pressure (Pascal)

 

 

 

 

 

 

 

 

 

 

 

 

25

50

75

100

125

150

174

199

 

224

249

274

 

m3/hr

RPM

kW

RPM

kW

RPM

kW

RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

3338

443

0.33

489

0.37

535

0.4

581

0.44

627

0.48

673

0.51

719

0.55

765

0.59

791

0.62

818

0.66

 

3547

453

0.34

499

0.39

546

0.43

592

0.47

638

0.51

684

0.55

730

0.59

771

0.63

798

0.67

825

0.72

 

3755

463

0.37

510

0.41

556

0.45

602

0.5

649

0.54

695

0.59

742

0.63

776

0.68

804

0.72

831

0.77

 

3964

473

0.38

520

0.43

567

0.48

613

0.52

660

0.57

706

0.62

753

0.67

782

0.72

810

0.77

838

0.82

 

4173

445

0.35

489

0.4

533

0.45

578

0.5

622

0.54

667

0.6

711

0.64

756

0.69

784

0.74

813

0.8

842

0.85

 

4381

464

0.37

506

0.43

548

0.47

589

0.51

631

0.57

672

0.61

714

0.66

757

0.71

786

0.75

815

0.81

844

0.87

 

4590

484

0.4

523

0.44

562

0.49

601

0.54

640

0.58

678

0.63

717

0.68

758

0.72

787

0.77

817

0.84

847

0.9

 

4798

504

0.42

540

0.46

576

0.51

612

0.55

648

0.6

684

0.65

720

0.69

759

0.74

789

0.78

819

0.86

850

0.92

 

5007

524

0.44

557

0.48

590

0.53

624

0.57

657

0.62

690

0.66

723

0.71

760

0.75

790

0.8

821

0.87

853

0.95

 

 

.75 kW Standard Motor

 

 

 

 

.75 kW Standard Motor

 

 

 

1.12 kW Oversized

Motor

 

 

and Low Static Drive

 

 

 

 

 

andDrive

 

 

 

 

 

 

and High Static Drive

 

 

Notes:

1.Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.

2.Tabulated brake horsepower is the motor shaft output required.

3.Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.

Table PD-16 — Blower Speeds — TWE075A

 

 

 

Motor DriveTurns Open

 

 

Drive

6

5

4

3

2

1

0

Standard

N/A

600

650

700

750

800

850

Low Static

N/A

428

464

499

535

571

606

High Static

N/A

700

750

800

850

900

950

SSP-PRC002-EN

Table PD-15 — Continued

 

 

 

External Static Pressure (Pascal)

 

 

 

 

 

299

 

324

349

374

398

 

m3/hr

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

3338

844

0.72

 

871

0.76

897

0.81

924

0.86

950

0.9

3547

852

0.77

 

879

0.81

906

0.87

933

0.91

 

3755

859

0.82

 

886

0.87

914

0.92

942

0.97

 

3964

866

0.87

 

894

0.92

922

0.97

950

1.02

 

4173

870

0.9

 

899

0.96

928

1.01

 

4381

874

0.93

 

903

0.99

932

1.06

 

4590

877

0.96

 

907

1.03

937

1.1

 

4798

880

0.99

 

911

1.07

942

1.13

 

5007

884

1.02

 

915

1.1

946

1.18

 

 

1.12 kW Oversized Motor and High Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 