Table PD-12 — Gross Heating Capacities (MBh)

Performance

Data(System)

Table PD-12 — Gross Heating Capacities (MBh)

TWA200B Heat Pump with TWE200B Air Handler At 6675 CFM (I-P)

Outdoor

Heating Capacity (BTUH/1000) At

 

Total Power in Kilowatts At

 

Temperature

Indicated Indoor Dry BulbTemperature

Indicated Indoor Dry BulbTemperature

(°F)

60

70

75

80

60

70

75

80

-18

42.4

79.1

84.7

87.4

11.5

15.4

16.6

17.6

-13

68.2

86.2

90.2

92.3

13.0

15.6

16.7

17.7

-8

81.5

93.8

96.7

98.0

13.6

15.9

16.9

17.9

-3

93.1

101.8

103.7

104.5

14.1

16.2

17.1

18.1

2

104.2

110.2

111.4

111.7

14.5

16.4

17.4

18.3

7

115.2

119.2

119.8

119.7

14.9

16.7

17.6

18.6

12

126.6

128.8

128.9

128.5

15.2

17.0

17.9

18.9

17

138.2

139.1

138.8

138.2

15.5

17.3

18.2

19.2

22

150.3

150.1

149.5

148.6

15.9

17.6

18.6

19.6

27

162.9

161.8

160.9

159.8

16.2

18.0

18.9

20.0

32

176.1

174.3

173.2

171.9

16.5

18.3

19.3

20.4

37

189.2

186.9

185.6

184.3

16.9

18.7

19.7

20.8

42

202.8

200.0

198.6

197.2

17.2

19.1

20.2

21.3

47

216.9

213.8

212.3

210.8

17.6

19.5

20.6

21.8

52

231.9

228.5

226.8

225.3

18.0

20.0

21.1

22.3

57

247.4

243.6

241.9

240.3

18.4

20.5

21.7

22.9

62

263.2

259.1

257.2

255.6

18.9

21.0

22.2

23.5

67

279.3

274.8

272.8

271.0

19.4

21.6

22.8

24.1

72

295.9

291.1

289.0

287.0

20.0

22.2

23.4

24.7

Table PD-12 — Gross Heating Capacities (kW)

TWA200B Heat Pump with TWE200B Air Handler At 11340 m3/h (SI)

Outdoor

 

Heating Capacity (kW) At

 

 

Total Power in Kilowatts At

 

Temperature

Indicated Indoor Dry BulbTemperature

Indicated Indoor Dry BulbTemperature

(°C)

15.6

21.1

23.9

26.7

15.6

21.1

23.9

26.7

-27.8

12.4

23.2

24.8

25.6

5.5

6.0

6.2

6.5

-25.0

20.0

25.3

26.4

27.0

5.6

6.1

6.3

6.6

-22.2

23.9

27.5

28.3

28.7

5.7

6.2

6.5

6.7

-19.4

27.2

29.8

30.4

30.6

5.8

6.3

6.6

6.9

-16.7

30.5

32.3

32.6

32.7

5.9

6.5

6.7

7.0

-13.9

33.7

34.9

35.1

35.1

6.0

6.6

6.9

7.2

-11.1

37.1

37.7

37.8

37.6

6.2

6.7

7.0

7.4

-8.3

40.5

40.7

40.7

40.5

6.3

6.9

7.2

7.5

-5.6

44.0

43.9

43.8

43.5

6.5

7.0

7.4

7.7

-2.8

47.7

47.4

47.1

46.8

6.6

7.2

7.5

7.9

0.0

51.6

51.0

50.7

50.3

6.8

7.4

7.7

8.1

2.8

55.4

54.7

54.3

54.0

6.9

7.6

7.9

8.3

5.6

59.4

58.6

58.1

57.7

7.1

7.8

8.1

8.5

8.3

63.5

62.6

62.2

61.7

7.3

8.0

8.4

8.8

11.1

67.9

66.9

66.4

66.0

7.5

8.2

8.6

9.0

13.9

72.4

71.3

70.8

70.3

7.7

8.4

8.8

9.2

16.7

77.1

75.9

75.3

74.8

7.9

8.7

9.1

9.5

19.4

81.8

80.5

79.9

79.4

8.1

8.9

9.3

9.8

22.2

86.6

85.2

84.6

84.0

8.4

9.2

9.6

10.0

Correction Factors - Other Airflows

 

Airflow = 6700 cfm (11383 m3/h)

(Table Value x Correction Factor = Value at new airflow)

Heating Capacity (High Temp.) = 214,000 (62.66)

 

 

 

Heating Capacity (Low Temp.) = 139,000 (40.70)

Airflow

6000 cfm

7325 cfm

Compressor Power (High Temp) = 15.83 kW

 

10194 m3/h 12445 m3/h

Compressor Power (Low Temp) = 13.50 kW

Heating Capacity

x0.99

x1.01

Coeff. Of Perf. (High Temp) = 3.2

Compressor kW

x1.02

x0.98

Coeff. Of Perf. (Low Temp) = 2.3

Values at ARI Rating Conditions of:

 

Outdoor Fan Power = 1,200 watts

70F (21.1C) and 47/43F (8.3/6.1C)(High Temp.Cond.)

Indoor Fan Power = 2,300 watts

70F (21.1C) and 17/15F (-8.3/-9.4C)(Low Temp. Cond)

 

Note:

1. Rated with 25 feet of 1-3/8” suction and 1/2" liquid line."