Trane TWA200B, TWA075A, TWE200B, TWE050A manual Performance Data, Total

Models: TWA200B TWA075A TWE200B TWE050A

1 56
Download 56 pages 34.19 Kb
Page 30
Image 30
Manual background

Performance

Data

Table PD-25 — Auxiliary Electric Heat Capacity — Air Handler

 

 

 

No.

 

 

Stage 1

 

 

Stage 2

 

Total

Unit

Total

of

 

kW

Btu

kW

kW

Btu

kW

Btu

kW

Model No.

kW

Stages

Input

Output

Output

Input

Output

Output

Output

Output

TWE050, 075,100

3.47

1

3.47

11,851

3.47

11,851

3.47

 

 

6.92

1

9.92

23,606

6.92

23,606

6.92

 

 

10.39

1

10.39

35,457

10.39

35,457

10.39

 

 

17.31

2

10.39

35,457

10.39

6.92

23,606

6.92

59,063

17.31

TWE075, 100A, 100

24.22

2

13.83

47,213

13.83

10.39

35,457

10.39

82,670

24.22

TWE155, 200

6.94

1

6.94

23,701

6.94

23,701

6.94

 

 

13.83

1

13.83

47,213

13.83

47,213

13.83

 

 

20.78

2

13.83

47,213

13.83

6.94

23,701

6.94

70,915

20.78

 

 

34,62

2

20.78

70,915

20.78

13.84

47,213

13.89

118,128

34.61

*Heaters are rated at 400v. For other than rated voltage,

 

 

 

 

 

 

 

Voltage

2

 

 

 

 

Voltage

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity = (Rated Voltage

) x Rated Capacity and kW = (Rated Voltage ) x Rated kW.

 

 

 