Trane TWE200B, TWA075A, TWA200B Performance, DataSystem, Table PD-10- Gross Heating Capacities MBh

Models: TWA200B TWA075A TWE200B TWE050A

1 56
Download 56 pages 34.19 Kb
Page 21
Image 21
Table PD-10 — Gross Heating Capacities (MBh)

Performance

Data(System)

Table PD-10 — Gross Heating Capacities (MBh)

TWA100A Heat Pump with TWE100A Air Handler At 3325 CFM (I-P)

Outdoor

Heating Capacity (Btu/1000) At

 

Total Power in Kilowatts At

 

Temperature

Indicated Indoor Dry BulbTemperature

Indicated Indoor Dry BulbTemperature

(°F)

60

70

75

80

60

70

75

80

-18

20.4

37.3

41.2

43.6

5.7

7.3

7.9

8.5

-13

31.4

41.8

44.6

46.4

6.2

7.5

8.0

8.6

-8

39.0

46.3

48.4

49.7

6.5

7.6

8.1

8.6

-3

45.5

50.8

52.4

53.3

6.8

7.8

8.2

8.7

2

51.8

55.6

56.7

57.3

7.0

7.9

8.4

8.8

7

57.9

60.6

61.3

61.6

7.2

8.0

8.5

9.0

12

64.1

65.8

66.2

66.3

7.3

8.2

8.6

9.1

17

70.4

71.3

71.4

71.3

7.5

8.3

8.7

9.2

22

76.9

77.1

77.0

76.7

7.6

8.4

8.9

9.4

27

83.6

83.3

82.9

82.5

7.8

8.6

9.0

9.5

32

90.7

89.7

89.2

88.7

7.9

8.8

9.2

9.7

37

97.6

96.2

95.5

94.9

8.1

8.9

9.4

9.9

42

104.6

102.9

102.1

101.4

8.2

9.1

9.6

10.1

47

112.0

109.9

109.0

108.2

8.4

9.3

9.7

10.3

52

119.5

117.2

116.2

115.2

8.6

9.5

10.0

10.5

57

127.1

124.6

123.5

122.5

8.8

9.7

10.2

10.7

62

134.8

132.1

130.8

129.7

9.0

9.9

10.4

11.0

67

142.6

139.7

138.3

137.2

9.2

10.1

10.7

11.2

72

150.7

147.5

146.1

144.8

9.4

10.4

10.9

11.5

Table PD-10 — Gross Heating Capacities (kW)

TWA100A Heat Pump with TWE100A Air Handler At 5649 m3/h (SI)

Outdoor

 

Heating Capacity (kW) At

 

 

Total Power in Kilowatts At

 

Temperature

Indicated Indoor Dry BulbTemperature

Indicated Indoor Dry BulbTemperature

(°C)

15.6

21.1

23.9

26.7

15.6

21.1

23.9

26.7

-27.8

6.0

10.9

12.1

12.8

5.5

6.0

6.2

6.5

-25.0

9.2

12.2

13.1

13.6

5.6

6.1

6.3

6.6

-22.2

11.4

13.5

14.2

14.6

5.7

6.2

6.5

6.7

-19.4

13.3

14.9

15.3

15.6

5.8

6.3

6.6

6.9

-16.7

15.2

16.3

16.6

16.8

5.9

6.5

6.7

7.0

-13.9

17.0

17.7

17.9

18.0

6.0

6.6

6.9

7.2

-11.1

18.8

19.3

19.4

19.4

6.2

6.7

7.0

7.4

-8.3

20.6

20.9

20.9

20.9

6.3

6.9

7.2

7.5

-5.6

22.5

22.6

22.5

22.5

6.5

7.0

7.4

7.7

-2.8

24.5

24.4

24.3

24.1

6.6

7.2

7.5

7.9

0.0

26.5

26.3

26.1

26.0

6.8

7.4

7.7

8.1

2.8

28.6

28.2

28.0

27.8

6.9

7.6

7.9

8.3

5.6

30.6

30.1

29.9

29.7

7.1

7.8

8.1

8.5

8.3

32.8

32.2

31.9

31.7

7.3

8.0

8.4

8.8

11.1

35.0

34.3

34.0

33.7

7.5

8.2

8.6

9.0

13.9

37.2

36.5

36.2

35.9

7.7

8.4

8.8

9.2

16.7

39.5

38.7

38.3

38.0

7.9

8.7

9.1

9.5

19.4

41.7

40.9

40.5

40.2

8.1

8.9

9.3

9.8

22.2

44.1

43.2

42.8

42.4

8.4

9.2

9.6

10.0

Correction Factors - Other Airflows

 

Airflow = 3325 cfm (5649 m3/h)

(Table Value x Correction Factor = Value at new airflow)

Heating Capacity (High Temp.) = 110,000 (32.21)

 

 

 

Heating Capacity (Low Temp.) = 71,000 (20.79)

Airflow

3000 cfm

3675 cfm

Compressor Power (High Temp) = 7.59 kW

 

5097 m3/h

6243 m3/h

Compressor Power (Low Temp) = 6.60 kW

Heating Capacity

x0.99

x1.01

Coeff. Of Perf. (High Temp) = 3.4

Compressor kW

x1.02

x0.98

Coeff. Of Perf. (Low Temp) = 2.4

 

 

 

Outdoor Fan Power = 615 watts

Values at ARI Rating Conditions of:

 

Indoor Fan Power = 1,030 watts

70F (21.1C) and 47/43F (8.3/6.1C)(High Temp.Cond.)

 

70F (21.1C) and 17/15F (-8.3/-9.4C)(Low Temp. Cond)

Note:

 

 

 

1. Rated with 25 feet of 1-3/8" suction and 1/2" liquid line.

SSP-PRC002-EN

21

Page 21
Image 21
Trane TWE200B Performance, DataSystem, Table PD-10- Gross Heating Capacities MBh, Table PD-10- Gross Heating Capacities kW