Trane TWA075A, TWE200B manual Air Handler, Performance, Data, Table PD-14- Blower Speeds - TWE050A

Models: TWA200B TWA075A TWE200B TWE050A

1 56
Download 56 pages 34.19 Kb
Page 24
Image 24
(Air Handler)

Performance

 

Data

(Air Handler)

Table PD-13 — Evaporator Fan Performance — TWE050A (I-P)

 

 

 

 

 

 

 

External Static Pressure (Inches of Water Column)

 

 

 

 

 

 

 

 

.10"

.20"

.30"

.40"

.50"

.60"

.70"

.80"

.90"

1.00"

1.10"

CFM

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1400

646

0.37

698

0.42

751

0.47

803

0.52

856

0.56

908

0.61

941

0.65

973

0.68 1006 0.71

1500

607

0.36

661

0.40

713

0.45

764

0.50

816

0.54

867

0.59

919

0.64

952

0.67

984

0.71

 

 

1600

625

0.38

676

0.43

727

0.48

778

0.52

828

0.57

879

0.62

930

0.67

963

0.70

995

0.74

1700

601

0.35

648

0.40

696

0.44

744

0.49

792

0.54

 

 

889

0.64

937

0.69

971

0.73

1005 0.77

841

0.59

1800

625

0.36

671

0.41

716

0.46

762

0.51

807

0.56

853

0.61

898

0.66

944

0.71

979

0.76

 

1900

642

0.40

687

0.45

731

0.50

776

0.55

820

0.60

865

0.66

909

0.71

951

0.75

987

0.80

 

2000

659

0.44

703

0.49

745

0.54

790

0.60

833

0.65

877

0.70

920

0.75

957

0.80

994

0.84

 

2100

674

0.48

722

0.54

770

0.60

817

0.65

857

0.70

897

0.75

936

0.80

973

0.85

1009 0.89

 

 

 

 

 

1.0 HP Oversized Motor and High Static Drive

 

 

 

 

 

0.75 HP Standard Motor and Standard Static Drive

 

 

 

 

 

 

Notes:

1.Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.

2.Tabulated brake horsepower is the motor shaft output required.

3.Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.

Table PD-13— Evaporator Fan Performance — TWE050A (SI)

 

 

 

External Static Pressure (Pascal)

 

 

 

 

25

50

75

100

125

150

174

199

224

249

274

m3/hr RPM kW

RPM kW

RPM kW

RPM kW

RPM kW

RPM kW

RPM kW

RPM kW

RPM kW

RPM kW

RPM kW

2379

 

646

0.28

698

0.31

751

0.35

803

0.39

856

0.42

908

0.45

941

0.48

2549

 

607

0.27

661

0.30

713

0.34

764

0.37

816

0.40

867

0.44

919

0.48

952

0.50

2718

625

0.28

676

0.32

727

0.36

778

0.39

828

0.43

879

0.46

930

0.50

963

0.52

2888

601

0.26

648

0.30

696

0.33

744

0.37

792

0.40

841

0.44

889

0.48

937

0.51

971

0.54

3058

625

0.27

671

0.31

716

0.34

762

0.38

807

0.42

853

0.45

898

0.49

944

0.53

979

0.57

3228

642

0.30

687

0.34

731

0.37

776

0.41

820

0.45

865

0.49

909

0.53

951

0.56

987

0.60

3398

659

0.33

703

0.37

745

0.40

790

0.45

833

0.48

877

0.52

920

0.56

957

0.60

994

0.63

3568

674

0.36

722

0.40

770

0.45

817

0.48

857

0.52

 

897

0.56

936

0.60

973

0.63

1009

0.66

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.56 kW Standard Motor and Standard Static Drive 0.75 kW Oversized Motor and High Static Drive

9730.51 1006 0.53

9840.53 — —

995 0.55 — —

1005 0.57 — —

— — — —

— — — —

— — — —

— — — —

Notes:

1.Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.

2.Tabulated brake horsepower is the motor shaft output required.

3.Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.

Table PD-14 — Blower Speeds — TWE050A

Drive

 

 

Motor DriveTurns Open

 

 

6

5

4

3

2

1

0

Standard

N/A

590

639

688

737

786

835

High Static

N/A

713

772

832

891

951

1009

24

SSP-PRC002-EN

Page 24
Image 24
Trane TWA075A, TWE200B, TWA200B manual Air Handler, Performance, Data, Table PD-14- Blower Speeds - TWE050A