Performance

Performance

Data

Table PD-23— Discharge Plenum And Grille Assembly Throw Distance — Air Handler — ft (m)

Unit

 

 

 

 

Louver Angle Deflection Position

 

Model No.

CFM

m3/h

 

Straight

20

40

55

 

1400

2378

38 (11.6)

24 (7.3)

22 (6.7)

18 (5.5)

 

1600

2718

42 (12.8)

31 (9.4)

26 (7.9)

20 (6.1)

TWE050

1800

3058

46 (14.0)

37 (11.3)

29 (8.8)

22 (6.7)

 

2000

3398

48 (14.6)

43 (13.1)

33 (10.1)

24 (7.3)

 

2200

3737

51 (15.5)

50 (15.2)

36 (11.0)

25 (7.6)

 

2100

3568

49 (14.9)

38 (11.6)

31 (9.4)

27 (8.2)

 

2400

4077

52 (15.9)

43 (13.1)

35 (10.7)

29 (8.8)

 

2700

4587

55 (16.8)

48 (14.6)

38 (11.6)

31 (9.4)

TWE075

3000

5097

58 (17.7)

53 (16.2)

42 (12.8)

32 (9.8)

 

3200

5436

56 (17.1)

46 (14.0)

38 (11.6)

30 (9.1)

 

3600

6116

62 (18.9)

51 (15.5)

42 (12.8)

33 (10.1)

 

4000

6795

66 (20.1)

57 (17.4)

47 (14.3)

35 (10.7)

 

4400

7475

71 (21.6)

62 (18.9)

52 (15.9)

38 (11.6)

TWE100

4800

8154

76 (23.2)

67 (20.4)

56 (17.1)

42 (12.8)

 

4300

7305

42 (12.8)

32 (9.8)

29 (8.8)

21 (6.4)

 

4900

8324

47 (14.3)

38 (11.6)

32 (9.8)

25 (7.6)

 

5400

9174

52 (15.9)

44 (13.4)

37 (11.3)

29 (8.8)

TWE155

5600

9514

50 (15.2)

40 (12.2)

33 (10.1)

27 (8.2)

 

6000

10193

57 (17.4)

49 (14.9)

41 (12.5)

32 (9.8)

 

6400

10873

56 (17.1)

46 (14.0)

38 (11.6)

30 (9.1)

 

7200

12232

62 (18.9)

51 (15.5)

42 (12.8)

33 (10.1)

TWE200

8000

13591

66 (20.1)

57 (17.4)

47 (14.3)

35 (10.7)

Throw distance values are based on a terminal velocity of 75 FPM (0.38 m/s).

Throw distance values at other terminal velocities may be established by multiplying throw distances in table above by throw

factor:

 

 

Terminal Velocity

 

Throw Factor

50 fpm (.25 m/s)

x

1.50

100 fpm (.51 m/s)

x

.75

150 fpm (.76 m/s)

x

.50

Table PD-24— Static Pressure Drop Through Accessories (Inches Of Water Column)1 — Air Handler

 

 

 

 

 

Discharge

 

 

Electric Heaters (kW)

 

Unit

 

 

Return Grille

Plenum and Grille2

5-10

15-20

25-30

35-50

Model No.

CFM

m3/h

In. wc1

Pascal

In. wc1

Pascal

 

 

In. wc (Pascal)

 

 

1400

2380

.09

(22.4)

.16

(39.8)

.06 (15.0)

.06 (15.0)

.12 (29.9)

TWE050A

1600

2718

.12

(29.9)

.21

(52.3)

08 (19.9)

.08 (19.9)

.14 (34.9)

 

2000

3398

.18

(44.8)

.33

(82.2)

.13 (32.4)

.13 (32.4)

.19 (47.3)

 

2100

3568

.05

(12.5)

.19

(47.3)

.02 (5.0)

.03 (7.5)

.05 (12.5)

.08 (19.9)

TWE075A

2400

4079

.08

(19.9)

.27

(67.2)

.03 (7.5)

.06 (15.0)

.08 (19.9)

.12 (29.9)

 

3000

5098

.13

(32.4)

.40

(99.6)

.06 (15.0)

.12 (29.9)

.17 (42.4)

.23 (57.3)

TWE100A

2800

4756

.04

(10.0)

.34

(84.7)

.03 (7.5)

.04 (10.0)

.14 (34.9)

.20 (49.8)

TWE100B

3200

5436

.07

(17.4)

.43

(107.1)

.06 (15.0)

.13 (32.4)

.19 (47.3)

.26 (64.8)

 

4300

7304

.07

(17.4)

.18

(44.8)

.02 (5.0)

.02 (5.0)

.04 (10.0)

.05 (12.5)

TWE155B

4800

8154

.09

(22.4)

.23

(57.3)

.03 (7.5)

.03 (7.5)

.06 (15.0)

.08 (19.9)

 

6000

10195

.15

(37.4)

.34

(84.7)

.06 (15.0)

.06 (15.0)

.12 (29.9)

.17 (42.4)

 

5600

9515

.07

(17.4)

.32

(79.7)

.04 (10.0)

.04 (10.0)

.10 (25.0)

.15 (37.4)

TWE200B

6400

10872

.11

(27.4)

.43

(107.1)

.06 (15.0)

.06 (15.0)

.13 (32.4)

.19 (47.3)

 

8000

13594

.17

(42.3)

.66

(164.3)

.10 (25.0)

.10 (25.0)

.20 (49.8)

.30 (74.7)

1.Return air filter ESP included in Fan PerformanceTable data.

2.At louver opening angle of 42°F (5.5°C). For ESP at other angle openings, see accessory Installer’s Guide.

SSP-PRC002-EN