Trane TWA075A, TWE200B, TWA200B, TWE050A manual Electrical Data, Heater

Models: TWA200B TWA075A TWE200B TWE050A

1 56
Download 56 pages 34.19 Kb
Page 32
Image 32
Heater

Electrical

Data

Table ED-5— UnitWiringWith Electric Heat (Single Point Connection) — Air Handlers

Heater

Heater

To Use

Control

Minimum

Maximum

Model No.

kW Rating1

with Unit

Stages

Circuit Ampacity 2

Fuse Breaker Size 2

BAYHTRL405A

3.47

 

1

 

9

15

BAYHTRL410A

6.92

TWE050AD

1

 

17

20

BAYHTRL415A

10.39

 

1

 

24

25

BAYHTRL425A

17.31

 

2

 

39

40

BAYHTRL405A

3.47

 

1

 

11

15

BAYHTRL410A

6.92

 

1

 

18

20

BAYHTRL415A

10.39

TWE075AD

1

 

26

30

BAYHTRL425A

17.31

 

2

 

41

45

BAYHTRL435A

24.22

 

2

 

56

60

BAYHTRL405A

3.47

 

1

 

12

15

BAYHTRL410A

6.92

 

1

 

19

25

BAYHTRL415A

10.39

TWE100AD,TWE100BD

1

 

27

30

BAYHTRL425A

20.78

 

2

 

42

45

BAYHTRL435A

24.22

 

2

 

57

60

BAYHTRM410A

6.94

 

1

 

21

30

BAYHTRM420A

13.83

TWE155BD

1

 

36

40

BAYHTRM430A

20.78

 

2

 

51

60

BAYHTRM450A

34.62

 

2

 

81

90

BAYHTRM410A

6.94

 

1

 

25

40

BAYHTRM420A

13.83

TWE200BD

1

 

40

50

BAYHTRM430A

20.78

 

2

 

55

60

BAYHTRM450A

34.62

 

2

 

85

90

1. kW ratings are at 400v for 3 phase, 400v air handlers

 

 

 

 

 

For other than rated voltage, ampacity = (RatedVoltageVoltage)2 x Rated Capacity and kW =

(RatedVoltageVoltage

)2

Rated kW.

 

2.Any power supply and circuits must be wired and protected in accordance with local codes.

3.Field wire must be rated at least 75°C.

4.Field wire must be rated at least 90°C.

32

SSP-PRC002-EN

Page 32
Image 32
Trane TWA075A, TWE200B, TWA200B, TWE050A manual Electrical Data, Heater