Electrical
Data
Table
Heater | Heater | To Use | Control | Minimum | Maximum | |
Model No. | kW Rating1 | with Unit | Stages | Circuit Ampacity 2 | Fuse Breaker Size 2 | |
BAYHTRL405A | 3.47 |
| 1 |
| 9 | 15 |
BAYHTRL410A | 6.92 | TWE050AD | 1 |
| 17 | 20 |
BAYHTRL415A | 10.39 |
| 1 |
| 24 | 25 |
BAYHTRL425A | 17.31 |
| 2 |
| 39 | 40 |
BAYHTRL405A | 3.47 |
| 1 |
| 11 | 15 |
BAYHTRL410A | 6.92 |
| 1 |
| 18 | 20 |
BAYHTRL415A | 10.39 | TWE075AD | 1 |
| 26 | 30 |
BAYHTRL425A | 17.31 |
| 2 |
| 41 | 45 |
BAYHTRL435A | 24.22 |
| 2 |
| 56 | 60 |
BAYHTRL405A | 3.47 |
| 1 |
| 12 | 15 |
BAYHTRL410A | 6.92 |
| 1 |
| 19 | 25 |
BAYHTRL415A | 10.39 | TWE100AD,TWE100BD | 1 |
| 27 | 30 |
BAYHTRL425A | 20.78 |
| 2 |
| 42 | 45 |
BAYHTRL435A | 24.22 |
| 2 |
| 57 | 60 |
BAYHTRM410A | 6.94 |
| 1 |
| 21 | 30 |
BAYHTRM420A | 13.83 | TWE155BD | 1 |
| 36 | 40 |
BAYHTRM430A | 20.78 |
| 2 |
| 51 | 60 |
BAYHTRM450A | 34.62 |
| 2 |
| 81 | 90 |
BAYHTRM410A | 6.94 |
| 1 |
| 25 | 40 |
BAYHTRM420A | 13.83 | TWE200BD | 1 |
| 40 | 50 |
BAYHTRM430A | 20.78 |
| 2 |
| 55 | 60 |
BAYHTRM450A | 34.62 |
| 2 |
| 85 | 90 |
1. kW ratings are at 400v for 3 phase, 400v air handlers |
|
|
|
|
| |
For other than rated voltage, ampacity = (RatedVoltageVoltage)2 x Rated Capacity and kW = | (RatedVoltageVoltage | )2 | Rated kW. |
|
2.Any power supply and circuits must be wired and protected in accordance with local codes.
3.Field wire must be rated at least 75°C.
4.Field wire must be rated at least 90°C.
32 |