Table GD-2 General Data — Heat Pumps
| TWA155B | TWA200B |
Cooling Performance1 |
|
|
Gross Cooling Capacity, Btu (kW) |
|
|
Matched Air Handler, Btu (kW) | 167,000 (48.9) | 218,000 (63.83) |
Condensing Unit Only2, Btu (kW) | 167,000 (48.9) | 218,000 (63.83) |
ARI Net Cooling Capacity3 | 162,000 (47.43) | 211,000 (61.78) |
System Power kW | 15.67 | 21.51 |
Condensing Unit Power kW | 13.91 | 19.1 |
Heating Performance |
|
|
ARI Heating with Matched Air Handler |
|
|
HighTemperature Capacity, Btu (kW) | 166,000 (48.6) | 214,000 (62.66) |
LowTemperature Capacity, Btu (kW) | 101,000 (29.57) | 139,000 (40.70) |
Compressor |
|
|
Number | 2 | 2 |
Type | 3D®Scroll | 3D®Scroll |
No. Motors | 2 | 2 |
Motor HP | 6.25 (4.7) | 8.33 (6.21) |
Motor RPM, (kW) | 2875 | 2875 |
ARI Sound Rating (Bels)4 | 8.8 | 8.8 |
System Data5 |
|
|
No. Refrigerant Circuits | 2 | 2 |
Suction Line, in. (mm) OD | 1.375 (34.9) | 1.375 (34.9) |
Liquid Line, in. (mm) OD | 0.500 (12.7) | 0.500 (12.7) |
Outdoor Coil | Plate Fin | Plate Fin |
Tube Size, in. (mm) OD | 0.375 (9.5) | 0.375 (9.5) |
Face Area, sq. ft (m2) | 38.4 (3.57) | 48 (4.46) |
Rows | 2 | 2 |
Fins Per Inch | 18 | 18 |
Outdoor FanType | Propeller | Propeller |
No. Used | 2 | 2 |
Diameter, in. (mm) | 26.00 (660.4) | 28.00 (711) |
DriveType | Direct | Direct |
No. Speeds | 1 | 1 |
CFM6, (m3/h) | 9800 (16650.2) | 13400 (22766.60) |
No. Motors | 2 | 2 |
Motor HP (kW) | 0.33 (.25) | 0.75 (.56) |
Motor RPM | 925 | 925 |
36.0 (16.33) | 48.5 (22.0) |
Notes:
1.Cooling Performance is rated at 95°F (35°C) ambient, 80°F (26.7°C) entering dry bulb, 67°F (19.4°C) entering wet bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for this product. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Rated accordance with ARI Standard
2.Condensing Unit Only Gross Cooling Capacity rated at 45°F (7.6°C) saturated suction temperature and at 95°F (35°C) ambient.
3.ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft (7.6 m) of 1.375, 0.500 OD interconnect- ing tubing. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. Integrated Part Load Value is based on ARI Standard
4.ARI Sound Rating is rated in accordance with ARI Standard 270 or 370.
5.System Data based on maximum linear length 80 ft (26.7 m)Maximum lift: suction 60 ft (18.3 m) liquid 60 ft (18.3 m) For greater lengths, refer to refrigerant piping applications manual.
6.Outdoor Fan cfm is rated with standard
7.Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft (7.6 m) of interconnecting refrigerant lines.
10 |