Performance | (Air Handler) |
Data |
Table
|
|
|
|
|
|
|
|
| External Static Pressure (In. Of Water Column) |
|
|
|
|
|
|
| |||||||||
| 0.10 | 0.20 | 0.30 | 0.40 | 0.50 | 0.60 | 0.70 | 0.80 | 0.90 | 1.00 | 1.20 | ||||||||||||||
CFM |
| RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP | |||||||||||||||||||||||
| 1.5 HP Standard Motor and Low Static Drive |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
2600 | 460 | 0.32 | 493 | 0.39 | 527 | 0.47 | 565 | 0.55 | 603 | 0.63 | 641 | 0.71 | 679 | 0.79 | 717 | 0.87 | 744 | 0.94 | 772 | 1.01 | 826 | 1.16 | |||
2775 | 473 | 0.37 | 506 | 0.45 | 540 | 0.53 | 576 | 0.61 | 613 | 0.69 | 649 | 0.77 | 686 | 0.85 | 723 | 0.93 | 748 | 1.00 | 775 | 1.07 | 830 | 1.20 | |||
2950 | 487 | 0.43 | 519 | 0.50 | 552 | 0.58 | 587 | 0.67 |
| 623 | 0.75 | 658 | 0.83 | 693 | 0.91 | 728 | 0.99 | 751 | 1.06 | 779 | 1.12 | 833 | 1.25 | ||
3125 | 501 | 0.49 | 532 | 0.56 | 565 | 0.64 | 599 | 0.72 | 632 | 0.81 | 666 | 0.89 | 700 | 0.97 | 734 | 1.05 | 755 | 1.11 | 783 | 1.18 | 737 | 1.30 | |||
3300 | 520 | 0.58 | 548 | 0.65 | 581 | 0.73 |
| 613 | 0.81 | 644 | 0.89 | 677 | 0.98 | 710 | 1.06 | 740 | 1.13 | 759 | 1.19 | 787 | 1.25 | 841 | 1.37 | ||
3475 | 541 | 0.69 | 568 | 0.76 | 600 | 0.84 | 631 | 0.93 | 658 | 1.00 | 691 | 1.08 | 721 | 1.16 | 746 | 1.21 | 764 | 1.28 | 793 | 1.34 | 846 | 1.48 | |||
3650 | 562 | 0.82 | 588 | 0.88 | 618 | 0.97 | 648 | 1.05 | 671 | 1.11 | 703 | 1.19 | 732 | 1.27 | 753 | 1.31 | 772 | 1.38 | 801 | 1.45 | 853 | 1.59 | |||
3825 |
| 582 | 0.96 | 608 | 1.03 | 637 | 1.11 | 666 | 1.20 | 685 | 1.26 | 711 | 1.31 | 739 | 1.38 | 763 | 1.44 | 787 | 1.51 | 815 | 1.58 | 862 | 1.74 | ||
4000 |
| 602 | 1.11 | 628 | 1.17 | 656 | 1.26 | 683 | 1.35 | 698 | 1.40 | 720 | 1.43 | 747 | 1.50 | 773 | 1.58 | 801 | 1.64 | 829 | 1.71 | 872 | 1.89 | ||
|
|
|
|
|
|
|
|
| 1.5 HP Standard Motor and Drive |
|
|
|
| 2.0 HP Oversized Motor | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| and High Static Drive |
Notes:
1.Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.
2.Tabulated brake horsepower is the motor shaft output required.
3.Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.
4.Low Static Drive must be field supplied.
Table PD-17— Continued
External Static Pressure (In. Of Water Column)
| 1.40 | 1.60 |
CFM | RPM BHP RPM BHP |
2.0HP Oversized Motor and High Static Drive
2600 881 1.30 936 1.45
2775 884 1.36 938 1.51
2960 886 1.41 939 1.57
3125 889 1.47 941 1.64
3300 892 1.54 945 1.73
3475 897 1.63 950 1.85
3650 902 1.73 955 1.99
3825 912 1.89 960 2.18
4000 922 2.04 965 2.30
Table | TWE100A, TWE100B (SI) |
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
| External Static Pressure (Pascal) |
|
|
|
|
|
|
|
|
| ||||||
| 25 | 50 | 75 | 100 | 125 | 150 | 174 | 199 | 224 | 249 | 299 | ||||||||||||
m3/hr | RPM | kW | RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW | ||||||||||||
1.12 kW Standard Motor and Low Static Drive |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
4417 | 460 | 0.24 | 493 | 0.29 | 527 | 0.35 | 565 | 0.41 | 603 | 0.47 | 641 | 0.53 | 679 | 0.59 | 717 | 0.65 | 744 | 0.7 | 772 | 0.75 | 826 | 0.87 | |
4715 | 473 | 0.28 | 506 | 0.34 | 540 | 0.4 | 576 | 0.45 | 613 | 0.51 | 649 | 0.57 | 686 | 0.63 | 723 | 0.69 | 748 | 0.75 | 775 | 0.8 | 830 | 0.89 | |
5012 | 487 | 0.32 | 519 | 0.37 | 552 | 0.43 | 587 | 0.5 | 623 | 0.56 | 658 | 0.62 | 693 | 0.68 | 728 | 0.74 | 751 | 0.79 | 779 | 0.84 | 833 | 0.93 | |
5309 | 501 | 0.37 | 532 | 0.42 | 565 | 0.48 | 599 | 0.54 | 632 | 0.6 | 666 | 0.66 | 700 | 0.72 | 734 | 0.78 | 755 | 0.83 | 783 | 0.88 | 737 | 0.97 | |
5607 | 520 | 0.43 | 548 | 0.48 | 581 | 0.54 | 613 | 0.6 | 644 | 0.66 | 677 | 0.73 | 710 | 0.79 | 740 | 0.84 | 759 | 0.89 | 787 | 0.93 | 841 | 1.02 | |
5904 | 541 | 0.51 | 568 | 0.57 |
| 600 | 0.63 | 631 | 0.69 | 658 | 0.75 | 691 | 0.8 | 721 | 0.87 | 746 | 0.9 | 764 | 0.95 | 793 | 1 | 846 | 1.1 |
6201 | 562 | 0.61 | 588 | 0.66 | 618 | 0.72 | 648 | 0.78 | 671 | 0.83 | 703 | 0.89 | 732 | 0.95 | 753 | 0.98 | 772 | 1.03 | 801 | 1.08 | 853 | 1.19 | |
6499 | 582 | 0.72 | 608 | 0.77 | 637 | 0.83 | 666 | 0.89 | 685 | 0.94 | 711 | 0.98 | 739 | 1.03 | 763 | 1.07 | 787 | 1.13 | 815 | 1.18 | 862 | 1.3 | |
6796 | 602 | 0.83 | 628 | 0.87 | 656 | 0.94 | 683 | 1.01 | 698 | 1.04 | 720 | 1.07 | 747 | 1.12 | 773 | 1.18 | 801 | 1.22 | 829 | 1.28 | 872 | 1.41 | |
|
|
|
|
|
|
| 1.12 kW Standard Motor and Drive |
|
|
| 1.49 kW Oversized Motor | ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| and High Static Drive |
Notes:
1.Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.
2.Tabulated brake horsepower is the motor shaft output required.
3.Factory setting of motor sheave is 3.0 turns open. Adjustments are made in 0.5 turn increments.
4.Low Static Drive must be field supplied.
Table PD - 18 — Blower Speeds — TWE100A,TWE100B
|
|
| Motor SheaveTurns Open |
|
| ||
Drive | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
Standard | N/A | 587 | 629 | 671 | 713 | 755 | 796 |
Low Static | N/A | 453 | 485 | 518 | 550 | 583 | 615 |
High Static | N/A | 606 | 641 | 677 | 713 | 748 | 784 |
High Static II N/A | 745 | 789 | 833 | 877 | 920 | 965 |
Table
External Static Pressure (Pascal)
349398
m3/hr RPM kW RPM kW
1.49kW Oversized Motor and High Static Drive
4417 881 0.97 936 1.08
4715 884 1.01 938 1.13
5012 886 1.05 939 1.17
5309 889 1.1 941 1.22
5607 892 1.15 945 1.29
5904 897 1.22 950 1.38
6201 902 1.29 955 1.48
6499 912 1.41 960 1.63
6796 922 1.52 965 1.72
26 |