Table PD-17— Continued

Performance

(Air Handler)

Data

Table PD-17 — Evaporator Fan Performance TWE100A, TWE100B (I-P)

 

 

 

 

 

 

 

 

 

External Static Pressure (In. Of Water Column)

 

 

 

 

 

 

 

 

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1.20

CFM

 

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

 

1.5 HP Standard Motor and Low Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2600

460

0.32

493

0.39

527

0.47

565

0.55

603

0.63

641

0.71

679

0.79

717

0.87

744

0.94

772

1.01

826

1.16

2775

473

0.37

506

0.45

540

0.53

576

0.61

613

0.69

649

0.77

686

0.85

723

0.93

748

1.00

775

1.07

830

1.20

2950

487

0.43

519

0.50

552

0.58

587

0.67

 

623

0.75

658

0.83

693

0.91

728

0.99

751

1.06

779

1.12

833

1.25

3125

501

0.49

532

0.56

565

0.64

599

0.72

632

0.81

666

0.89

700

0.97

734

1.05

755

1.11

783

1.18

737

1.30

3300

520

0.58

548

0.65

581

0.73

 

613

0.81

644

0.89

677

0.98

710

1.06

740

1.13

759

1.19

787

1.25

841

1.37

3475

541

0.69

568

0.76

600

0.84

631

0.93

658

1.00

691

1.08

721

1.16

746

1.21

764

1.28

793

1.34

846

1.48

3650

562

0.82

588

0.88

618

0.97

648

1.05

671

1.11

703

1.19

732

1.27

753

1.31

772

1.38

801

1.45

853

1.59

3825

 

582

0.96

608

1.03

637

1.11

666

1.20

685

1.26

711

1.31

739

1.38

763

1.44

787

1.51

815

1.58

862

1.74

4000

 

602

1.11

628

1.17

656

1.26

683

1.35

698

1.40

720

1.43

747

1.50

773

1.58

801

1.64

829

1.71

872

1.89

 

 

 

 

 

 

 

 

 

1.5 HP Standard Motor and Drive

 

 

 

 

2.0 HP Oversized Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and High Static Drive

Notes:

1.Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.

2.Tabulated brake horsepower is the motor shaft output required.

3.Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.

4.Low Static Drive must be field supplied.

Table PD-17— Continued

External Static Pressure (In. Of Water Column)

 

1.40

1.60

CFM

RPM BHP RPM BHP

2.0HP Oversized Motor and High Static Drive

2600 881 1.30 936 1.45

2775 884 1.36 938 1.51

2960 886 1.41 939 1.57

3125 889 1.47 941 1.64

3300 892 1.54 945 1.73

3475 897 1.63 950 1.85

3650 902 1.73 955 1.99

3825 912 1.89 960 2.18

4000 922 2.04 965 2.30

Table PD-17— Evaporator Fan Performance

TWE100A, TWE100B (SI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Pascal)

 

 

 

 

 

 

 

 

 

 

25

50

75

100

125

150

174

199

224

249

299

m3/hr

RPM

kW

RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.12 kW Standard Motor and Low Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4417

460

0.24

493

0.29

527

0.35

565

0.41

603

0.47

641

0.53

679

0.59

717

0.65

744

0.7

772

0.75

826

0.87

4715

473

0.28

506

0.34

540

0.4

576

0.45

613

0.51

649

0.57

686

0.63

723

0.69

748

0.75

775

0.8

830

0.89

5012

487

0.32

519

0.37

552

0.43

587

0.5

623

0.56

658

0.62

693

0.68

728

0.74

751

0.79

779

0.84

833

0.93

5309

501

0.37

532

0.42

565

0.48

599

0.54

632

0.6

666

0.66

700

0.72

734

0.78

755

0.83

783

0.88

737

0.97

5607

520

0.43

548

0.48

581

0.54

613

0.6

644

0.66

677

0.73

710

0.79

740

0.84

759

0.89

787

0.93

841

1.02

5904

541

0.51

568

0.57

 

600

0.63

631

0.69

658

0.75

691

0.8

721

0.87

746

0.9

764

0.95

793

1

846

1.1

6201

562

0.61

588

0.66

618

0.72

648

0.78

671

0.83

703

0.89

732

0.95

753

0.98

772

1.03

801

1.08

853

1.19

6499

582

0.72

608

0.77

637

0.83

666

0.89

685

0.94

711

0.98

739

1.03

763

1.07

787

1.13

815

1.18

862

1.3

6796

602

0.83

628

0.87

656

0.94

683

1.01

698

1.04

720

1.07

747

1.12

773

1.18

801

1.22

829

1.28

872

1.41

 

 

 

 

 

 

 

1.12 kW Standard Motor and Drive

 

 

 

1.49 kW Oversized Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and High Static Drive

Notes:

1.Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.

2.Tabulated brake horsepower is the motor shaft output required.

3.Factory setting of motor sheave is 3.0 turns open. Adjustments are made in 0.5 turn increments.

4.Low Static Drive must be field supplied.

Table PD - 18 — Blower Speeds — TWE100A,TWE100B

 

 

 

Motor SheaveTurns Open

 

 

Drive

6

5

4

3

2

1

0

Standard

N/A

587

629

671

713

755

796

Low Static

N/A

453

485

518

550

583

615

High Static

N/A

606

641

677

713

748

784

High Static II N/A

745

789

833

877

920

965

Table PD-17— Continued

External Static Pressure (Pascal)

349398

m3/hr RPM kW RPM kW

1.49kW Oversized Motor and High Static Drive

4417 881 0.97 936 1.08

4715 884 1.01 938 1.13

5012 886 1.05 939 1.17

5309 889 1.1 941 1.22

5607 892 1.15 945 1.29

5904 897 1.22 950 1.38

6201 902 1.29 955 1.48

6499 912 1.41 960 1.63

6796 922 1.52 965 1.72