Trane WC-IOM-7 manual Heavy Objects, Improper Unit Lift, Typical weights and point loading data

Models: WC-IOM-7

1 60
Download 60 pages 56.23 Kb
Page 19
Image 19
Heavy Objects!

Unit Dimensions

￿WARNING

Heavy Objects!

Do not use cables (chains or slings) except as shown. Each of the cables (chains or slings) used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements may cause equipment or property-only damage. Failure to properly lift unit may result in death or serious injury. See details below.

￿WARNING

Improper Unit Lift!

Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage.

Table 1.

Typical weights and point loading data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Center of

 

 

 

Corner Weights (lbs.)

Gravity (in.)

 

 

 

 

 

 

 

 

Unit

 

Net

A

B

C

D

Length Width

Description

Weight

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WC*150B

 

1375

465

344

231

311

46

29

 

 

 

 

 

 

 

 

 

WC*155B

 

1412

547

638

231

343

43

27

 

 

 

 

 

 

 

 

 

WC*180B

 

1412

547

638

231

343

43

27

 

 

 

 

 

 

 

 

 

WC*200B

 

1916

640

497

340

438

51

34

 

 

 

 

 

 

 

 

 

WC*240B

 

1916

640

497

340

438

51

34

 

 

 

 

 

 

 

 

 

Note: Corner weights are given for information only. Unit is to be supported continuously by a curb or equivalient frame support.

Figure 8. Rigging and center of gravity data

WC-IOM-7 • Packaged Heat Pump

19

Page 19
Image 19
Trane WC-IOM-7 manual Heavy Objects, Improper Unit Lift, Typical weights and point loading data, Unit Dimensions