Installation
Note: Resistance in excess of 2.5 ohms per conductor can cause deviations in the accuracy of the controls.
2.Ensure that the wiring between controls and the unit’s termination point does not exceed two and a half (2.5) ohms/conductor for the length of the run.
3.Do not run the electrical wires transporting DC signals in or around conduit housing high voltage wires.
Table 3. DC Conductors Zone Sensor Module wiring
Distance from Unit to Control Recommended Wire Size
0 - 150 feet | 22 gauge | |
|
| |
0 - 45.7 m | .33 mm2 | |
|
|
|
151 | - 240 feet | 20 gauge |
|
|
|
46 | - 73.1 m | .50 mm2 |
|
| |
241 | 18 gauge | |
|
| |
73.5 - 117.3 m | .75 mm2 | |
|
|
|
386 | - 610 feet | 16 gauge |
|
| |
117.7 - 185.9 m | 1.3 mm2 | |
|
|
|
611 | - 970 feet | 14 gauge |
|
| |
186.2 - 295.7 m | 2.0 mm2 | |
|
|
|