Installation
•Check the supply fan belts for proper tension and the fan bearings for sufficient lubrication. If the belts require adjustment, or if the bearings need lubricating, refer to the maintenance section of this manual for instructions.
•Verify that a condensate trap is installed and the piping is properly sized and pitched.
•Verify that the correct size and number of filters are in place.
•Inspect the interior of the unit for tools and debris and install all panels in preparation for starting the unit.
Voltage Imbalance
Three phase electrical power to the unit must meet stringent requirements for the unit to operate properly. Measure each leg
Excessive three phase voltage imbalance between phases will cause motors to overheat and eventually fail. The maximum allowable voltage imbalance is 2%. Measure and record the voltage between phases 1, 2, and 3 and calculate the amount of imbalance as follows:
% Voltage Imbalance =
100⎛ AV – VD⎞ ⎝
AV
where Average Voltage (AV);
AV= | ⎛ Volt1 + Volt2 + Volt3⎞ | ||
⎝ | ⎠ |
V1, V2, V3 = Line Voltage Readings
VD = Line Voltage reading that deviates the farthest from the average voltage.
Example: If the voltage readings of the supply power measured 221, 230, and 227, the average volts would be:
221 + 230 + 227 2.2percent
VD (reading farthest from average) = 221
The percentage of Imbalance equals:
100⎛ 226 – 221⎞ 2.2percent ⎝
226
The 2.2% imbalance in this example exceeds the maximum allowable imbalance of 2.0%. This much imbalance between phases can equal as much as a 20% current imbalance with a resulting increase in motor winding temperatures that will decrease motor life. If the voltage imbalance is over 2%, notify the proper agencies to correct the voltage problem before operating this equipment.