Troubleshooting

Zone Temperature Sensor (ZTS) Test

Note: These procedures are not for programmable or digital models and are conducted with the Zone Sensor Module electrically removed from the system.

Test 1

Zone Temperature Thermistor (ZTEMP)

This component is tested by measuring the resistance between terminals 1 and 2 on the Zone Temperature Sensor. Below are some typical indoor temperatures, and corresponding resistive values.

Table 8.

 

 

Nominal

Nominal CSP

 

 

ZTEMP

or HSP

Zone Temperature

Resistance

Resistance

 

 

 

 

50 F°

10.0 C°

19.9 K-Ohms

889 Ohms

 

 

 

 

55 F°

12.8 C°

17.47 K-Ohms

812 Ohms

 

 

 

 

60 F°

15.6 C°

15.3 K-Ohms

695 Ohms

 

 

 

 

65 F°

18.3 C°

13.49 K-Ohms

597 Ohms

 

 

 

 

70 F°

21.1 C°

11.9 K-Ohms

500 Ohms

 

 

 

 

75 F°

23.9 C°

10.50 K-Ohms

403 Ohms

 

 

 

 

80 F°

26.7 C°

9.3 K-Ohms

305 Ohms

 

 

 

 

85 F°

29.4 C°

8.25 K-Ohms

208 Ohms

 

 

 

 

90 F°

32.2 C°

7.3 K-Ohms

110 Ohms

 

 

 

 

Test 2

Cooling Set Point (CSP) and Heating Set Point (HSP)

The resistance of these potentiometers are measured between the following ZSM terminals. Refer to the chart above for approximate resistances at the given setpoints.

Cool SP = Terminals 2 and 3

Range = 100 to 900 Ohms approximate

Heat SP = Terminals 2 and 5

Range = 100 to 900 Ohms approximate