Trane WC-IOM-7 manual Pre-Start, Test Modes, Service test guide for component operation

Models: WC-IOM-7

1 60
Download 60 pages 56.23 Kb
Page 35
Image 35
Pre-Start

Pre-Start

Test Modes

There are three methods in which the “Test” mode can be cycled at LTB-Test 1 and LTB-Test 2.

1.Step Test Mode - This method initiates the different components of the unit, one at a time, by temporarily shorting across the two test terminals for two to three seconds.

For the initial start-up of the unit, this method allows the technician to cycle a component “On” and have up to one hour to complete the check.

2.Resistance Test Mode - This method can be used for start-up providing a decade box for variable resistance outputs is available. This method initiates the different components of the unit, one at a time, when a specific resistance value is placed across the two test terminals. The unit will remain in the specific test mode for approximately one hour even though the resistance is left on the test terminals.

3.Auto Test Mode - This method is not recommended for start-up due to the short timing between individual component steps. This method initiates the different components of the unit, one at a time, when a jumper is installed across the test terminals. The unit will start the first test step and change to the next step every 30 seconds. At the end of the test mode, control of the unit will automatically revert to the applied "System" control method.

For unit test steps, test modes, and step resistance values to cycle the various components, refer to Table 5.

Table 5.

Service test guide for component operation

 

 

 

 

 

 

 

 

 

 

 

 

 

TEST

 

 

Econ

 

 

 

 

 

STEP

MODE

Fan

(Note 2)

Comp 1

Comp 2

Heat 1

Heat 2

Ohms

 

 

 

 

 

 

 

 

 

 

1

 

Fan

On

Minimum

Off

Off

Off

2.2K

 

 

 

 

 

Position Off

 

 

 

 

 

 

 

 

 

Setpoint 0%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

On

Selectable

Off

Off

Off

Off

 

 

 

Ventilation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

Economizer

On

Open

Off

Off

Off

Off

3.3K

 

 

Test Open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

Cool Stage 1

On

Minimum

(Note 1)

Off

Off

Off

4.7K

 

 

 

 

Position

On

 

 

 

 

 

 

 

 

 

 

 

 

 

4

(Note 3) Cool Stage 2

On

Minimum

(Note 1)

(Note 1)

Off

Off

6.8K

 

 

 

 

Position

On

On

 

 

 

 

 

 

 

 

 

 

 

 

5

(Note 3) Reheat

On

Minimum

On

On

Off

Off

33K

 

 

 

 

 

 

 

 

 

6

(Note 3) Heat Stage 1

On

Minimum

Off

Off

On

Off

10K

 

 

 

 

 

 

 

 

 

7

(Note 3) Heat Stage 2

On

Minimum

Off

Off

On

On

15K

Notes:

1 - The condenser fans will operate any time a compressor is "On" providing the outdoor air temperatures are within the operating values. 2 - The exhaust fan will turn on anytime the economizer damper position is equal to or greater than the exhaust fan setpoint.

3 - Steps for optional accessories and non-applicable modes in unit will be skipped.

WC-IOM-7 • Packaged Heat Pump

35

Page 35
Image 35
Trane WC-IOM-7 manual Pre-Start, Test Modes, Service test guide for component operation