Pre-Start
Test Modes
There are three methods in which the “Test” mode can be cycled at
1.Step Test Mode - This method initiates the different components of the unit, one at a time, by temporarily shorting across the two test terminals for two to three seconds.
For the initial
2.Resistance Test Mode - This method can be used for
3.Auto Test Mode - This method is not recommended for
For unit test steps, test modes, and step resistance values to cycle the various components, refer to Table 5.
Table 5. | Service test guide for component operation |
|
|
|
| ||||
|
|
|
|
|
|
|
|
| |
TEST |
|
| Econ |
|
|
|
|
| |
STEP | MODE | Fan | (Note 2) | Comp 1 | Comp 2 | Heat 1 | Heat 2 | Ohms | |
|
|
|
|
|
|
|
|
|
|
1 |
| Fan | On | Minimum | Off | Off | Off | 2.2K |
|
|
|
|
| Position Off |
|
|
|
|
|
|
|
|
| Setpoint 0% |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Minimum | On | Selectable | Off | Off | Off | Off |
|
|
| Ventilation |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 |
| Economizer | On | Open | Off | Off | Off | Off | 3.3K |
|
| Test Open |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 |
| Cool Stage 1 | On | Minimum | (Note 1) | Off | Off | Off | 4.7K |
|
|
|
| Position | On |
|
|
|
|
|
|
|
|
|
|
|
|
| |
4 | (Note 3) Cool Stage 2 | On | Minimum | (Note 1) | (Note 1) | Off | Off | 6.8K | |
|
|
|
| Position | On | On |
|
|
|
|
|
|
|
|
|
|
|
| |
5 | (Note 3) Reheat | On | Minimum | On | On | Off | Off | 33K | |
|
|
|
|
|
|
|
|
| |
6 | (Note 3) Heat Stage 1 | On | Minimum | Off | Off | On | Off | 10K | |
|
|
|
|
|
|
|
|
| |
7 | (Note 3) Heat Stage 2 | On | Minimum | Off | Off | On | On | 15K |
Notes:
1 - The condenser fans will operate any time a compressor is "On" providing the outdoor air temperatures are within the operating values. 2 - The exhaust fan will turn on anytime the economizer damper position is equal to or greater than the exhaust fan setpoint.
3 - Steps for optional accessories and
35 |