Troubleshooting

4.Verify all modes of operation, by running the unit through all of the steps in the “Test Modes” section discussed in “Unit Start-Up”.

5.After verifying proper unit operation, exit the test mode. Turn the fan on continuously at the ZSM, by pressing the button with the fan symbol. If the fan comes on and runs continuously, the ZSM is good. If you are not able to turn the fan on, the ZSM is defective.\

Table 9.

System mode and fan selection chart

 

 

 

 

 

Resistance Valves

Zone Sensor

 

Local Fan

(Ohms)

 

Unit/Fan Mode

Local Unit Mode

Mode

 

 

 

 

 

2.32K

 

Off/ Auto

Off

Auto

 

 

 

 

 

4.87K

 

Cool/Auto

Cool

Auto

 

 

 

 

 

7.68K

 

Auto/Auto

Auto

Auto

 

 

 

 

 

10.77K

 

Off/On

Off

On

 

 

 

 

 

13.32K

 

Cool/On

Cool

On

 

 

 

 

 

16.13K

 

Auto/On

Auto

On

 

 

 

 

 

19.48K

 

Heat/Auto

Heat

Auto

 

 

 

 

 

27.93K

 

Heat/On

Heat

On

 

 

 

 

 

35.0K

 

Emergency Heat/Auto

Emergency Heat

Auto

 

 

 

 

 

43.45K

 

Emergency Heat/On

Emergency Heat

On

 

 

 

 

Out of Range (Short)

INVALID/Short

Invalid (CV), Auto (VAV)

Invalid

 

 

 

 

Out of Range (Open)

INVALID/Open

Invalid (CV), Off (VAV)

Invalid

 

 

 

 

 

ReliaTel Refrigeration Module (RTRM) Default Chart

If the RTCI loses input from the building management system, the RTRM will control in the default mode after approximately 15 minutes. If the RTRM loses the Heating and Cooling setpoint input, the RTRM will control in the default mode instantaneously. The temperature sensing thermistor in the Zone Sensor Module is the only component required for the “Default Mode” to operate.

Unit Operation without a Zone Sensor

This procedure is for temporary operation only. The economizer and condenser fan cycling functions are disabled.

1.Open and Lock the unit disconnect switch.

2.Remove the Outside Air Sensor (OAS) from the condenser section of unit.

3.Use two (2) wire nuts, to individually cap the wires.

4.Locate the RTRM (J6). Connect two (2) wires to terminals J6-1 and 2.

5.Connect the sensor (OAS) using two wire nuts to the two (2) field supplied wires that were connected to terminals 1 and 2 on J6.

54

Packaged Heat Pump • WC-IOM-7

Page 54
Image 54
Trane WC-IOM-7 manual ReliaTel Refrigeration Module Rtrm Default Chart, Unit Operation without a Zone Sensor