Trane WC-IOM-7 Condensate Drain Configuration, Filter Installation, Field Installed Power Wiring

Models: WC-IOM-7

1 60
Download 60 pages 56.23 Kb
Page 23
Image 23
Condensate Drain Configuration

Installation

Connect properly sized control wiring to the proper termination points between the zone thermostat and the unit control panel.

Condensate Drain Configuration

An evaporator condensate drain connection is provided on each unit. Refer to

Unit Dimensions for the appropriate drain location.

A condensate trap must be installed at the unit due to the drain connection being on the “negative pressure” side of the fan. Install the P-Trap using the guidelines in Figure 9.

A condensate drain line must be connected to the P-Trap. Pitch the drain lines at least 1/2 inch for every 10 feet of horizontal run to assure proper condensate flow. Do not allow the horizontal run to sag causing a possible double-trap condition which could result in condensate backup due to “air lock”.

Figure 9. Condensate Trap Installation

Filter Installation

Each unit ships with 2 inch filters installed. The quantity of filters is determined by unit size. Access to the filters is obtained by removing the indoor fan access panel.

Refer to the unit Service Facts (shipped with each unit) for filter requirements.

Note: Do not operate the unit without filters.

Field Installed Power Wiring

An overall dimensional layout for the standard field installed wiring entrance into the unit is illustrated in Unit Dimensions. To insure that the unit’s supply power wiring is properly sized and installed, follow the guidelines outlined below.

WC-IOM-7 • Packaged Heat Pump

23

Page 23
Image 23
Trane WC-IOM-7 manual Condensate Drain Configuration, Filter Installation, Field Installed Power Wiring