Trane WC-IOM-7 manual Start Up, Economizer Start-Up, Rotating Components, Compressor Start-Up

Models: WC-IOM-7

1 60
Download 60 pages 56.23 Kb
Page 38
Image 38
Start Up

Start Up

Economizer Start-Up

ReliaTel Control

Using the Service Test Guide in Table 5, p. 35, momentarily jump across the Test 1 & Test 2 terminals on LTB1 one time to start the Minimum Ventilation Test.

1.Set the minimum position setpoint for the economizer to the required percentage of minimum ventilation using the setpoint potentiometer located on the Economizer Control (ECA).

The economizer will drive to its minimum position setpoint, exhaust fans (if applicable) may start at random, and the supply fan will start when the SERVICE TEST is initiated.

￿WARNING

Rotating Components!

During installation, testing, servicing and troubleshooting of this product it may be necessary to measure the speed of rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions when exposed to rotating components could result in death or serious injury.

The Exhaust Fan will start anytime the economizer damper position is equal to or greater than the exhaust fan setpoint.

2.Verify that the dampers stroked to the minimum position.

3.Momentarily jump across the Test 1 & Test 2 terminals on LTB one additional time if continuing from previous component start-up or until the desired start-up component Test is started.

4.Verify that the dampers stroked to the full open position.

5.To stop the SERVICE TEST, turn the main power disconnect switch to the “Off” position or proceed to the next component start-up procedure. Remove electro mechanical test mode connections (if applicable).

Compressor Start-Up

1.Attach a set of service gauges onto the suction and discharge gauge ports for each circuit. Refer to the refrigerant circuit illustration in the Service Facts.

Using the Service Test Guide in Table 5, p. 35, continue the SERVICE TEST start-up procedure for each compressor circuit.

Momentarily jump across the Test 1 & Test 2 terminals on LTB1 one additional time if continuing from previous component start-up or until the desired start-up component Test is started.

WC-IOM-7 • Packaged Heat Pump

38

Page 38
Image 38
Trane WC-IOM-7 manual Start Up, Economizer Start-Up, Rotating Components, Compressor Start-Up, ReliaTel Control