Trane WC-IOM-7 manual Cooling Season, Filters, Return Air Smoke Detector Maintenance

Models: WC-IOM-7

1 60
Download 60 pages 56.23 Kb
Page 43
Image 43
Filters

Maintenance

Filters

Inspect the return air filters. Clean or replace them if necessary. Refer to the unit Service Facts for filter information.

Return Air Smoke Detector Maintenance

Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coil and filters. To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector, complete adherence to the maintenance procedures, including recommended intervals between filter changes, and coil cleaning is required.

Periodic checks and maintenance procedures must be performed on the smoke detector to insure that it will function properly. For detailed instructions concerning these checks and procedures, refer to the appropriate section(s) of the smoke detector Installation and Maintenance Instructions provided with the literature package for this unit.

Cooling Season

Check the unit’s drain pans and condensate piping to ensure that there are no blockages.

Inspect the evaporator and condenser coils for dirt, bent fins, etc. If the coils appear dirty, clean them according to the instructions described in “Coil Cleaning” later in this section.

Manually rotate the condenser fan(s) to ensure free movement and check motor bearings for wear. Verify that all of the fan mounting hardware is tight.

Inspect the F/A-R/A damper hinges and pins to ensure that all moving parts are securely mounted. Keep the blades clean as necessary.

Verify that all damper linkages move freely; lubricate with white grease, if necessary.

Check supply fan motor bearings; repair or replace the motor as necessary.

Check the fan shaft bearings for wear. Replace the bearings as necessary.

Check the supply fan belt. If the belt is frayed or worn, replace it. Refer to the “Fan Belt Adjustment” section for belt replacement and adjustments.

Verify that all wire terminal connections are tight.

Remove any corrosion present on the exterior surfaces of the unit and repaint these areas.

Generally inspect the unit for unusual conditions (e.g., loose access panels, leaking piping connections, etc.)

Make sure that all retaining screws are reinstalled in the unit access panels once these checks are complete.

WC-IOM-7 • Packaged Heat Pump

43

Page 43
Image 43
Trane WC-IOM-7 manual Cooling Season, Filters, Return Air Smoke Detector Maintenance