Trane WC-IOM-7 NOTICE Use Copper Conductors Only, Main Unit Power, Standard Wiring, Installation

Models: WC-IOM-7

1 60
Download 60 pages 56.23 Kb
Page 24
Image 24
NOTICE

Installation

Note: All field installed wiring must conform to NEC guidelines as well as State and Local codes.

Verify that the power supply available is compatible with the unit’s nameplate ratings. The available supply power must be within 10% of the rated voltage stamped on the nameplate. Use only copper conductors to connect the power supply to the unit.

NOTICE

Use Copper Conductors Only!

Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage. Failure to do so may cause damage to the equipment.

Note: If the unit is not equipped with an optional factory installed nonfused disconnect switch or circuit breaker, a field supplied disconnect switch must be installed at or near the unit in accordance with the National Electrical Code (NEC latest edition).

Main Unit Power

Standard Wiring

The electrical service must be protected from over current and short circuit conditions in accordance with NEC requirements. Protection devices must be sized according to the electrical data on the nameplate.

1.If the unit is not equipped with an optional factory installed nonfused disconnect switch or circuit breaker, a field supplied disconnect switch must be installed at or near the unit in accordance with the National Electrical Code (NEC latest edition).

2.Location of the applicable electrical service entrance is illustrated in Unit Dimensions. Complete the unit’s power wiring connections onto either; the main terminal block HTB1 inside the unit control panel, the factory mounted nonfused disconnect switch (UCD) or circuit breaker (UCB), or the electric heat terminal block. Refer to the customer connection diagram that shipped with the unit for specific termination points.

3.Provide proper grounding for the unit in accordance with local and national codes.

Optional TBUE Wiring

(Through the Base Electrical Option)

1.Location of the applicable electrical service is illustrated in the following illustration. Refer to the customer connection diagram that is shipped with the unit for specific termination points. The termination points, depending on the customer option selected would be a factory mounted nonfused disconnect switch (UDC) or circuit breaker (UCB).

24

Packaged Heat Pump • WC-IOM-7

Page 24
Image 24
Trane WC-IOM-7 NOTICE Use Copper Conductors Only, Main Unit Power, Standard Wiring, Optional TBUE Wiring, Installation