VII. INTELA-TRAUL®(continued)

VII. n - STARTING A MANUAL DEFROST CYCLE:

This parameter allows a service technician to start a defrost cycle at any time. This parameter will override any lockout settings.

Follow the instructions to enter the customer access code on page 11. When the control

displays

 

 

 

 

 

Thermostat Set High, press the down arrow key

 

until the control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

display reads

 

 

 

 

 

 

Start Manual Defrost.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the set button SET .

The display will show

(NO).

Press either arrow key

(YES).

The display will show

.

Press the set button SET .

 

The display will then read Thermostat Set Point High.

You can use the up or down arrow keys to scroll to the next parameter

or press the alarm cancel button to exit

)) .

)

Reach-In/Roll-In Models

INTELA-TRAUL

°F°C

 

 

 

 

 

 

The defrost icon will be lit,

 

SET

 

and the display will read

 

 

 

 

))

 

 

 

 

 

 

 

 

 

 

 

)

 

 

 

 

 

 

 

 

 

when the unit is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in defrost.

 

 

 

 

 

 

FREEZER

 

 

 

 

 

DEFROST ICON

 

 

 

 

 

 

 

 

 

 

 

NOTE: Traulsen refrigerator units also have an off-cycle defrost once an hour, at which time the

control will read . This defrost is temperature terminated and can last from 3 - 10 minutes (dEF will be displayed for 22-27 minutes).