Traulsen R & A Series VII. INTELA-TRAUL continued, VII. p - ADJUSTING THE DOOR PERIMETER HEATERS

Models: R & A Series

1 28
Download 28 pages 1.89 Kb
Page 19
Image 19
VII. p - ADJUSTING THE DOOR PERIMETER HEATERS:

VII. INTELA-TRAUL®(continued)

VII. p - ADJUSTING THE DOOR PERIMETER HEATERS:

This parameter allows the customer to turn ON and OFF the anti-condensate door perimeter heaters. This parameter is set to the highest setting (100) at the factory so that the door heaters stay on continu- ously. If you choose to have the door heaters cycle on and off, lower this parameter to approximately 30. If condensation forms around the doors, increase the parameter until condensation stops. The exact setting will vary depending on ambient conditions. This feature is not available on undercounter mod- els.

Follow the instructions to enter the customer access code on page 11. When the control displays

 

 

 

 

 

 

 

Thermostat Set High, press the down arrow key

 

until the control display reads

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DewPoint Compensation Factor. Press the set button SET .

Press the arrow keys

 

 

 

 

to

 

 

 

 

 

adjust the factor to your desired setting. When the display shows the factor you want press the set

button SET . The display will then read VII. q - ADJUSTING THE ROOM TEMPERATURE OFFSET:Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background Thermostat Set Point High. You can use the up or

down arrow keysManual backgroundManual background to scroll to the next parameter or press the alarm cancel button to exit

Manual backgroundManual background))) .

VII. q - ADJUSTING THE ROOM TEMPERATURE OFFSET:

The room temperature offset parameter allows a service technician or end user the ability to have the display show a temperature that is within three degrees of the actual temperature being read by the cabinet air sensor. This allows for continuity of reading between different temperature reading devices. (i.e.: thermistor Vs thermocouple Vs handheld thermometer) This parameter is preset at the factory to “0” or no offset.

Follow the instructions to enter the customer access code on page 11. When the control displays

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background Thermostat Set High, press the down arrow keyManual backgrounduntil the control display reads

Room Temperature Offset. Press the set button SET . Use the arrow keys Manual backgroundManual background to adjust the offset to your desired setting. When the display shows the offset you want press the set button SET .

The display will then read Manual backgroundManual backgroundManual background Thermostat Set Point High. You can use the up or down arrow

keys

to scroll to the next parameter or press the alarm cancel button to exit

) .

 

 

))

-18-

Page 19
Image 19
Traulsen R & A Series owner manual VII. INTELA-TRAUL continued, VII. p - ADJUSTING THE DOOR PERIMETER HEATERS