SNMP Solo
If the SNMP Solo detects three communication failures in a row, the red LED turns on and stays on until the SNMP Solo receives a successful communication from the UPS.
Establish Network Communications
1.PING SNMP Solo.
Issue a PING command from the NMS. If you do not get a response, check the SNMP Solo’s network connection and IP address.
2.Test the adapter with an NMS.
Perform a “get” command and a “set” command. If either command fails, check the SNMP Solo access controls. The manager must have read permission to execute a get command successfully and read/write permission to execute a set command successfully.
(See the Configuring the NMS section for a detailed discussion.)
Your SNMP Solo SNMP adapter is now installed and completely functional.