Tyco 4100U-S1 installation manual SW1 to SW3 settings have no effect on Slave T-GEN 50s

Models: 4100U-S1

1 138
Download 138 pages 24.63 Kb
Page 80
Image 80

Using T-Gen 50 with 4100U-S1, Continued

T-Gen 50 Settings for NAC Operation

These switch and link settings should be used. These apply to T-GEN 50 software version 1.7.

 

Alert to Evacuate

 

 

Change-Over Time

 

SW1

 

SW2 (T1)

 

SW3

Setting on T-GEN 50

(T0)

 

 

 

(T2)

 

OFF

 

OFF

 

OFF

0 sec

ON

 

OFF

 

OFF

30 sec

OFF

 

ON

 

OFF

1 min

ON

 

ON

 

OFF

1.5 min

OFF

 

OFF

 

ON

3 min

ON

 

OFF

 

ON

5 min

OFF

 

ON

 

ON

10 min

ON

 

ON

 

ON

Alert Only

SW1 to SW3 settings have no effect on Slave T-GEN 50s.

SWITCH

Name

Setting on T-GEN 50

SW4

ALM I/P

OFF (Supervision disabled)

 

Supervision

 

SW5

ALM I/P

OFF (Non-latching)

 

 

 

SW6

Evac Tone

OFF

SW7

 

OFF for AS 2220 tone

 

 

ON for ISO 8201 + Keywords

SW8

Evac Message

OFF for Evac Message 1 or Field

 

 

Recorded message,

 

 

ON for Evac Message 2 or Keywords

 

 

only in ISO 8201

Link

Name

Setting on T-GEN 50

 

1

BIAS

Can be FITTED if PA or Background

 

 

 

Music not required

 

2

MASTER

FITTED

 

3

REC EN

Fit to record message.

 

4

TEST

Fit for test tone during installation

 

5

SLAVE

NOT FITTED

 

6

SLAVE / MASTER

MASTER

 

7

FAULT=

RELAY

 

 

DEF-/RELAY

 

 

 

 

 

 

5-12