![](/images/new-backgrounds/1055395/55395159x1.webp)
Using T-Gen 50 with 4100U-S1, Continued
These switch and link settings should be used. These apply to
| Alert to Evacuate |
|
| ||
| |||||
SW1 |
| SW2 (T1) |
| SW3 | Setting on |
(T0) |
|
|
| (T2) |
|
OFF |
| OFF |
| OFF | 0 sec |
ON |
| OFF |
| OFF | 30 sec |
OFF |
| ON |
| OFF | 1 min |
ON |
| ON |
| OFF | 1.5 min |
OFF |
| OFF |
| ON | 3 min |
ON |
| OFF |
| ON | 5 min |
OFF |
| ON |
| ON | 10 min |
ON |
| ON |
| ON | Alert Only |
SW1 to SW3 settings have no effect on Slave T-GEN 50s.
SWITCH | Name | Setting on |
SW4 | ALM I/P | OFF (Supervision disabled) |
| Supervision |
|
SW5 | ALM I/P | OFF |
|
|
|
SW6 | Evac Tone | OFF |
SW7 |
| OFF for AS 2220 tone |
|
| ON for ISO 8201 + Keywords |
SW8 | Evac Message | OFF for Evac Message 1 or Field |
|
| Recorded message, |
|
| ON for Evac Message 2 or Keywords |
|
| only in ISO 8201 |
Link | Name | Setting on |
|
1 | BIAS | Can be FITTED if PA or Background |
|
|
| Music not required |
|
2 | MASTER | FITTED |
|
3 | REC EN | Fit to record message. |
|
4 | TEST | Fit for test tone during installation |
|
5 | SLAVE | NOT FITTED |
|
6 | SLAVE / MASTER | MASTER |
|
7 | FAULT= | RELAY |
|
|
|
| |
|
|
|
|