Step 3. Configuring Cards, Continued

CPU Daughter Card Configuration

SPS Configuration

PDI Configuration

Configuring Other Cards

Note: Some devices that connect to RUI have inherently grounded shield terminals, in which case 24 C cannot be used. If 24 C is used, a Negative Ground Fault will occur.

P10/P11: P10 is associated with Port 1 and P11 is associated with Port 2. P10 and P11 are used to set the CPU motherboard up to be attached to either a network card or a RS- 232/2120 card.

Position 1 – 2: Network card (NIC) plugged into CPU motherboard (default).

Position 2 – 3: RS-232/2120 card plugged into CPU motherboard.

The CPU daughter card must be jumpered as follows:

P1 is used for engineering diagnostics (COMLAB). Normally has no link fitted.

Position 1 – 2 : Download or no connection.

Position 2 – 3 : Diagnostic mode.

P3 configures the RAM battery as ON or OFF.

Position 1 – 2 : ON – move to this position for normal operation.

Position 2 – 3 : OFF – factory setting.

The SPS must be configured as follows:

SW1: Using DIP switch SW1, set the SPS card address to 1. Use the address table in Appendix A for the switch settings.

P2: P2 configures the IDNet shield connection.

Position 1 – 2 (bottom) : Connects the shield to 0 V (default). Use this setting for 4100U-S1.

Position 2 – 3 (top) : Connects the shield to earth ground.

P3 configures relay 3 on the 4100-6033 Alarm Relay Card.

Position 1 – 2 (top) : Removes fault monitoring on Relay 3 (default). Use this setting for 4100U-S1.

Position 2 – 3 (bottom) : Makes Relay 3 activate when there is a fault.

P1: Earth connect jumper.

Position 1 – 2 (rhs): Enables Earth fault monitoring. Set to this position unless the system uses a TrueAlert Power Supply under common 0 V. Use this setting for 4100U-S1.

Position 2 – 3 (lhs): Disables Earth fault monitoring. Set to this position only if the system uses a TrueAlert Power Supply under common 0 V.

P4/P5: The PDI can be configured to draw its power from different sources via P4 and P5. For 4100U-S1 both links should be in position 1-2.

Refer to the appropriate installation instructions to configure other cards that are located in the CPU and expansion bays. The common 4100U cards and modules are included in this manual. Refer to Appendix D for a list of publications.

2-10

Page 28
Image 28
Tyco 4100U-S1 installation manual Configuring Cards

4100U-S1 specifications

The Tyco 4100U-S1 is a sophisticated and robust fire alarm control panel known for its reliability and advanced features, catering primarily to commercial and industrial applications. This system represents the latest in fire safety technology, providing comprehensive protection for a wide range of environments.

One of the main features of the Tyco 4100U-S1 is its ability to support advanced signaling protocols. This capability allows for seamless communication with a variety of initiating devices and notification appliances, ensuring a rapid response to potential fire incidents. The control panel can accommodate a significant number of devices connected through its extensive loop options, enhancing its flexibility in larger installations.

The Tyco 4100U-S1 employs Intelligent Addressable Technology, which simplifies the installation process and reduces wiring complexity. Each device on the loop can communicate its status without needing additional wiring, making it easier to troubleshoot and maintain. This feature not only enhances the system's efficiency but also helps to minimize installation costs.

Another notable characteristic of the Tyco 4100U-S1 is its user-friendly interface. The panel is designed for ease of use, featuring intuitive controls and a clear display that allows users to monitor the system’s status quickly. The graphical interface provides real-time information about the system’s performance, giving users insight into alarm conditions and system health. This accessibility aids in training personnel and encourages adherence to safety protocols.

The Tyco 4100U-S1 also boasts advanced reporting capabilities, with programmable inputs and outputs that allow for detailed event logging and alarm management. The system can be configured to send notifications via various channels, ensuring that key personnel are alerted immediately in case of an emergency. This proactive approach to fire safety helps organizations mitigate risks and enhance response strategies.

In addition, the Tyco 4100U-S1 integrates well with other building management systems, supporting various communication protocols that facilitate interoperability. This integration capability allows users to create a comprehensive safety network that addresses not only fire protection but also other critical building functions.

Overall, the Tyco 4100U-S1 stands out in the fire alarm control panel market with its combination of advanced technology, intuitive design, and extensive flexibility, making it an ideal choice for organizations seeking robust fire safety solutions. Its features and characteristics ensure that it remains a top contender in enhancing life safety and property protection.