DV360/580 Series Direct Vent Gas Fireplace

Troubleshooting the Gas Control System

START

•TURN GAS SUPPLY OFF NO

TURN ON/OFF SWITCH TO CALL FOR HEAT "ON"

POWER TO MODULE

(24V NORMAL)

YESManual background

SPARK ACROSS NO IGNITOR SENSOR GAP

YES

• TURN GAS ON

NO

PILOT BURNER LIGHTS?

YES

SPARK STOPS WHEN NO PILOT IS LIT?

YES

CHECK: • LINE VOLTAGE (120VAC)

LOW VOLTAGE TRANSFORMER (19.5 minimum VAC)

ON/OFF SWITCH

WIRING CONNECTIONS

UNPLUG IGNITION LEAD

NO

 

AND CHECK SPARK

 

• REPLACE MODULE

AT MODULE

 

 

 

(24VAC normal)

 

 

SPARK OK?

YES Manual background

CHECK IGNITION CABLE GROUND WIRING, CERAMIC INSULATOR AND GAP. CORRECT AS NECESSARY

CHECK BOOT OF IGNITION CABLE FOR SIGNS OF MELTING OR BUCKLING. TAKE PROTECTIVE ACTION TO SHIELD

CABLE AND BOOT FROM EXCESSIVE TEMPERATURES.

CHECK THAT ALL MANUAL GAS VALVES ARE OPEN, SUPPLY TUBING AND PRESSURES ARE GOOD, AND PILOT BURNER ORIFICE

IS NOT BLOCKED.

CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND PILOT OPERATOR ON GAS CONTROL.

CHECK FOR 24VAC ACROSS PV-MVPV TERMINALS ON MODULE IF VOLTAGE IS OKAY, REPLACE GAS CONTROL IF NOT, REPLACE MODULE.

NOTE: IF S8600B GOES INTO LOCKOUT, RESET SYSTEM.

CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE.

CLEAN FLAME ROD

CHECK ELECTRICAL CONNECTIONS BETWEEN FLAME ROD & MODULE.

CHECK FOR CRACKED CERAMIC FLAME ROD INSULATOR.

CHECK THAT PILOT FLAME COVERS FLAME ROD AND IS STEADY BLUE

ADJUST PILOT FLAME.

IF PROBLEM PERSISTS, REPLACE MODULE.

MAIN BURNER LIGHTS?

YES

NO

CHECK FOR 24VAC ACROSS MV-MVPV TERMINALS IF NO VOLTAGE, REPLACE MODULE.

CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND GAS CONTROL. IF OKAY, REPLACE GAS CONTROL, OR GAS CONTROL OPERATOR.

SYSTEM RUNS UNTIL NO ON/OFF SWITCH IS IN

"OFF" POSITION YES

TROUBLESHOOTING

ENDS

NOTE: IF S8600B GOES INTO LOCKOUT, RESET SYSTEM

CHECK FOR CONTINUITY OF IGNITION CABLE AND GROUND WIRE. NOTE: IF GROUND IS POOR OR ERRATIC, SHUTDOWN MAY OCCUR OCCASIONALLY EVEN THOUGH OPERATION IS NORMAL AT THE TIME OF CHECKOUT.

CHECK THAT THE PILOT FLAME COVERS FLAME ROD AND IS STEADY AND BLUE.

IF CHECKS ARE OKAY, REPLACE MODULE.