Electrical

DVHVAC36

Electrical

Refer to Figure 8 for field wiring.

1.Select fuse and wire size according to rating plate amperage.

2.Install a separate fused disconnect switch near the unit for service purposes.

3.Knockouts are provided on both sides of cabinet for electrical wiring.

4.Install room thermostat (24 volt) according to instructions provided with thermostat, using 18 gauge wire or larger.

5.Electrically ground the unit in accordance with local codes, or in the absence of local codes in accordance with the Canadian Electrical Code, Part 1 (CSA Standard C22.1) in Canada, or with the National Electric Code (ANSI/NFPA No. 70) in the United States.

6.The circuit board is equipped with two (2) accessory terminals. The terminal marked "Air Cleaner" and "Humidifier" are rated for 120V 0.5 Amps and are energized with the air circulating blower. Connect the neutral leg of the accessory to the 120V neutral wire.

 

 

 

 

 

 

 

 

EMERGENCY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THERMOPILE

 

 

 

 

SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GAS VALVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TP/TH

TP

TH

 

 

14 YELLOW

15 BLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLAME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

13 BLUE

 

 

 

 

 

ADJUST

 

 

 

 

 

 

 

 

 

WHITE

 

 

 

 

 

 

 

 

 

 

 

ACB

 

 

 

 

 

 

12 YELLOW

 

 

16 YELLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIMIT

 

 

 

 

 

 

 

 

 

COMMON

NOT USED

 

 

 

NOT USED

 

 

10 BLUE

 

 

 

17 GREEN

 

 

 

 

 

 

 

MED-HI

MED-LO

LOW

 

 

 

 

 

 

 

 

 

TH

ORANGE/BLACK ORANGE

 

 

 

 

 

 

 

 

 

 

11 GREEN

 

 

TP/TH

BROWN

 

 

 

1

2

3

4

5

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

4

 

 

 

 

CHASSIS GND

24 VAC RTN

24 VAC HOT TP

TH TP-PILE +

 

TH-PILE +

 

 

 

 

 

 

 

 

 

 

THERMOSTAT

R

4 RED

 

 

 

 

 

 

 

 

 

 

 

HUMIDIFIER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 RED

 

 

 

 

 

 

 

W1

5 WHITE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACB HEAT

 

 

 

 

 

 

 

G

18 GRAY

 

 

 

 

 

 

 

 

 

 

3 BLACK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACB COOL

 

 

 

 

 

 

 

Y

19 YELLOW

 

 

 

 

 

 

 

 

 

 

AIR CLEANER

 

 

 

 

 

3

5

GND

20 GREEN

 

 

 

 

 

 

 

 

 

 

XFORMER 1

 

 

 

 

 

9 YELLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

110 VAC HOT

 

 

 

 

 

 

 

 

 

 

 

SOLENOID 1

 

SOLENOID 2

 

 

 

X FORMER 2

ACB RTN

10 VAC RTN

HUMID RTN

CLEAN RTN

 

 

 

 

 

 

 

6 BLACK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7 WHITE

 

 

 

 

 

 

 

 

 

 

 

 

 

1 WHITE

 

 

 

 

 

 

 

8 BLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

110 VAC HOT

 

L1

 

 

 

8 BLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

110 VAC RTN

 

L2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP1413

Fig. 8 DVHVAC36 wiring diagram.

General Venting

This model is approved to be vented either through the side wall, or vertically through the roof.

Only venting components specifically approved and labelled for this fireplace may be used.

Minimum clearances between vent pipes and com- bustible materials is 1" (25 mm).

Venting terminals shall not be recessed into a wall or siding.

Horizontal venting must be installed on a level plane without an inclining or declining slope.

There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within

24" (610 mm) from the front of the termination hood.

Do not locate termination hood where excessive snow or ice build up may occur. Be sure to check vent termi- nation area after snow falls, and clear to prevent ac- cidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.

Location of Vent Termination

It is imperative that the vent termination be located ob- serving the minimum clearances as shown on Page 10.

*Check with local codes or in absence of same with CSA B149.1 Installation Codes (1991) for Canada or for U.S.A. Installations follow the current National Fuel Gas Code, ANSI Z223.1/NFPA 54.