Vermont Casting DVHVAC36 manual Troubleshooting the Gas Control System, Symptom, Possible Causes

Models: DVHVAC36

1 32
Download 32 pages 10.27 Kb
Page 24
Image 24
Troubleshooting the Gas Control System

DVHVAC36

Troubleshooting the Gas Control System

SIT NOVA 825 Millivolt Valve

NOTE: Before troubleshooting the gas control system, be sure external gas shut off is in the "ON" position.

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

1. Spark ignitor will not light

A. Defective or misaligned

Using a match, light pilot. If pilot lights, turn off

 

electrode at pilot.

pilot and push the red button again. If pilot will not

 

 

light - check gap at electrode and pilot-should be

 

 

1/8" to have a strong spark.

 

 

 

 

B. Defective ignitor (Push Button)

Push Piezo Ignitor Button. Check for spark at

 

 

electrode and pilot. If no spark to pilot, and elec

 

 

trode wire is properly connected, replace ignitor.

2. Pilot will not stay lit after

A. Defective pilot generator

Check pilot flame. Must impinge on thermo-

carefully following lighting

(thermocouple)

couple/thermopile. Note: this pilot burner assem

instructions.

 

bly utilizes both-a thermocouple and a thermopile.

 

 

The thermocouple operates the main valve

 

 

operation (On and Off). Clean and or adjust pilot for

 

 

maximum flame impingement on thermopile and

 

 

thermocouple.

 

 

 

 

B. Defective automatic valve

Turn valve knob to “Pilot”. Maintain flow to pilot;

 

 

millivolt meter should read greater than 10 mV. If

 

 

the reading is okay and the pilot does not stay on,

 

 

replace the gas valve. Note: An interrupter block

 

 

(not supplied) must be used to conduct this test.

3. Pilot burning, no gas to

A. Thermostat or wires defective

Check wall switch and wires for proper connections.

main burner, Valve knob

 

 

 

 

"ON", thermostat "ON"

B. Thermopile may not be

1. Be sure wire connections from thermopile at

 

generating sufficient

gas valve terminals are tight and thermopile is

 

millivoltage.

fully inserted into pilot bracket.

 

 

2. One of the wall switch wires may be grounded.

 

 

Remove wall switch wires from valve terminals if

 

 

pilot now stays lit, trace wall switch wiring for

 

 

ground. May be grounded to fireplace or gas

 

 

supply.

 

 

3. Check thermopile with millivolt meter. Take

 

 

reading at thermopile terminals of gas valve.

 

 

Should read 325 millivolts while holding valve

 

 

knob depressed in pilot position and wall switch

 

 

“Off”. Replace faulty thermopile if reading is below

 

 

specified minimum.

 

 

 

 

C. Plugged burner orifice.

Check burner orifices for debris and remove.

 

 

 

 

D. Defective automatic valve

Turn valve knob to “On”, place wall switch to “On”

 

operator.

millivolt meter should read greater than 100 mV. If

 

 

the reading is okay and the burner does not come

 

E. Transformer defective.

on, replace the gas valve.

 

 

 

F. Power Not ON.

 

 

G. heat demand satisfied.

 

4. Frequent pilot outage

A. Pilot flame may be too low

Clean and/or adjust pilot flame for maximum flame

problem.

or blowing (high) causing the

impingement on thermopile and thermocouple.

 

pilot safety to drop out.

 

 

 

 

 

B. Possible blockage of the vent

Check the vent terminal for blockage

 

terminal.

 

 

 

 

24

10001195

Page 24
Image 24
Vermont Casting DVHVAC36 Troubleshooting the Gas Control System, Symptom, Possible Causes, Corrective Action, 10001195