9-6. TROUBLESHOOTING FLOW
OPERATION INDICATOR lamp flashes
Indoor fan does not operate.
A Check of indoor fan motor
The indoor fan motor error has occurred, and the indoor fan doesn't operate.
Turn OFF the power supply.
|
|
|
|
|
| Pay careful attention to the high voltage on the fan motor connector CN211. | |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| Turn ON the power supply, wait 5 seconds or more, and then press |
| ||
|
|
|
|
|
| EMERGENCY OPERATION switch. |
|
|
|
| Is there any foreign matter that |
|
|
| Measure the supply voltage as follows within 12 seconds after EMER- |
| |||
|
|
|
| GENCY OPERATION switch is pressed. |
|
|
| ||
| interferes the rotation of the line |
|
|
|
|
|
| ||
| flow fan? |
| No |
| If more than 12 seconds passes by, turn OFF the power supply and |
| |||
|
|
|
| turn ON it again, then measure the voltage. |
|
| |||
|
|
|
|
|
|
|
| ||
|
| Yes |
|
|
| 1.Measure the voltage between CN211 | (+) and |
| |
|
|
|
| ||||||
|
|
|
|
| 2.Measure the voltage between CN211 | (+) and |
| ||
|
|
|
|
|
|
| |||
|
|
|
|
|
| If more than 12 seconds or more passes after EMERGENCY OPERATION | |||
|
|
|
|
| |||||
| Remove the foreign matter and |
|
|
| |||||
| adjust the line flow fan. |
|
|
| switch is pressed, the voltage mentioned above 2 goes 0 VDC although | ||||
|
|
|
|
|
| the indoor electronic control P.C. board is normal |
|
| |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
Is there 294/325 VDC between |
|
|
| ||
CN211 (+) and |
|
| Indoor electronic | ||
voltage between CN211 (+) and |
|
| |||
| Replace the indoor fan motor. | control P.C. board | |||
Yes | |||||
|
| ||||
within 12 seconds after EMERGEN- |
|
|
| ||
CY OPERATION switch is pressed? |
|
|
| ||
| No |
|
|
| |
|
|
|
| ||
|
|
|
|
|
CN211
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan repeats
Measure the voltage between CN211 (+) and
Is it unchanged holding
0 or 15 VDC?No (Changed)
Yes
(Unchanged)
Replace the indoor fan motor.
Replace the indoor electronic control P.C. board.
25