Vermont Casting MSY-D36NA, MSZ-D36NA Operating Range, Outlet Air Speed And Coverage Range

Models: MSY-D30NA MSZ-D36NA MSY-D36NA MSZ-D30NA

1 36
Download 36 pages 27.5 Kb
Page 6
Image 6
3-1. OPERATING RANGE

3-1. OPERATING RANGE

(1) POWER SUPPLY

 

Rated voltage

 

Guaranteed Voltage

 

 

 

 

 

 

 

 

208/230 V

Min.187 V 208 V 230 V Max.253 V

Indoor unit

1 phase

 

 

 

 

 

 

 

 

 

 

 

60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

(2) OPERATION

Mode

Condition

 

 

Intake air temperature (°F)

 

 

Indoor

 

 

Outdoor

 

 

DB

 

WB

DB

 

WB

 

Standard temperature

80

 

67

95

 

Cooling

Maximum temperature

90

 

73

115

 

Minimum temperature

67

 

57

14

 

 

 

 

 

Maximum humidity

78

%

 

 

Heating

Standard temperature

70

 

60

47

 

43

Maximum temperature

80

 

67

75

 

65

 

Minimum temperature

70

 

60

14

 

13

3-2. OUTLET AIR SPEED AND COVERAGE RANGE

Model

Mode

Function

Airlow

Air speed

Coverage

(CFM)

(ft./sec.)

range (ft.)

 

 

 

MSZ-D30NA

HEAT

Dry

848

23.6

45.0

MSZ-D36NA

 

 

 

 

 

MSZ-D30NA

 

Dry

848

23.6

45.0

MSZ-D36NA

COOL

 

 

 

 

MSY-D30NA

Wet

763

21.3

40.7

 

MSY-D36NA

 

 

 

 

 

 

 

 

 

 

 

 

3-2. OUTLET AIR SPEED AND COVERAGE RANGE The air coverage range is the figure up to the position where the air speed is 1 ft./sec., when air is blown out horizon- tally from the unit properly at the High speed position.

The coverage range should be used only as a general guideline since it var- ies according to the size of the room and furniture arranged inside the room.

6

Page 6
Image 6
Vermont Casting MSY-D36NA, MSZ-D36NA, MSZ-D30NA, MSY-D30NA service manual Operating Range, Outlet Air Speed And Coverage Range