8-9. EMERGENCY/TEST OPERATION
In case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the indoor unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of the remote controller run down. The unit will start and OPERATION INDICATOR lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The Indoor fan speed runs at High speed and the system is in continuous operation (with thermostat ON).
After 30 minutes of test run operation the system shifts to EMERGENCY COOL / HEAT MODE with a set temperature of 75 °F (24 °C). The fan speed shifts to Med.
All protective operations such as the coil frost prevention works even in emergency operation.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO ( ) mode.
Emergency operation continues until EMERGENCY OPERATION switch is pressed once or twice or the unit receives any signal from the remote controller. In case of latter normal operation will start.
NOTE : Do not press EMERGENCY OPERATION switch during normal operation.
E.O.
SW
E.O.
Operation mode | COOL | HEAT | |
(MUZ) | |||
|
| ||
Set temperature | 75 °F (24 °C) | 75 °F (24 °C) | |
Fan speed | Med. | Med. | |
Horizontal vane | Auto | Auto |
The operation mode is indicated by the Operation Indicator lamp as following
Operation Indicator lamp (MSZ type)
EMERGENCY COOL |
EMERGENCY OPERATION switch
SW
↓ | Lighted | |
Not lighted | ||
| ||
EMERGENCY HEAT |
|
↓
STOP
(MSY type)
EMERGENCY COOL
↓
STOP
8-10. 3-MINUTE TIME DELAY OPERATION
When the system turns OFF, compressor will not restart for 3 minutes as
8-11. CHANGING TEMPERATURE INDICATION (°F /°C)
•The preset unit is °F.
•°F→°C : Press RESET button while the
temperature buttons are pressed.
• °C→°F : Press RESET button or remove the batteries .
Press RESET button gently using a thin stick.
18