9-2. FAILURE MODE RECALL FUNCTION

Outline of the function

This air conditioner can memorize the abnormal condition which has occurred once.

Even though LED indication listed on the troubleshooting check table (9-4.) disappears, the memorized failure details can be recalled.

This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.

1. Flow chart of failure mode recall function for the indoor/outdoor unit

Operational procedure

The cause of abnormality cannot be found because the abnormality doesn't recur.

Setting up the failure mode recall function

Turn ON the power supply. <Preparation of the remote controller>

While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button.

First, release RESET button.

And release the other two buttons after all LCD in operation display section of the remote controller is displayed after 3 seconds.

Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1

 

 

 

 

 

 

 

 

 

1. Regardless of normal or abnormal condition, a short

 

Does the left lamp of OPERATION INDICATOR

 

 

 

 

beep is emitted once the signal is received.

 

lamp on the indoor unit blink at the interval of 0.5

 

 

 

Indoor unit is normal.

 

seconds?

 

 

 

 

But the outdoor unit might be abnormal because there are some abnor-

 

Blinks: Either indoor or outdoor unit is abnormal.

 

 

 

malities that can't be recalled with this way.

 

 

No

 

Beep is emitted at the same timing as the

 

Confirm if outdoor unit is abnormal according to the detailed outdoor unit

 

 

(OFF)

 

blinking of the left lamp of OPERATION

 

failure mode recall function.

 

INDICATOR lamp.

2

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Judgment of indoor/outdoor abnormality

 

 

(Blinks)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Before blinking, does the left lamp of OP-

 

 

 

 

 

 

 

ERATION INDICATOR lamp stay ON for 3

 

 

 

 

 

 

 

seconds?

 

 

 

 

 

 

 

 

Stays ON for 3 seconds (without beep):

Yes

 

 

 

 

 

 

 

 

 

 

 

The outdoor unit is abnormal.

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The indoor unit is abnormal.

Check the blinking pattern, and confirm the abnormal point with the indoor unit failure mode table. (Refer to 9-2.2)

Make sure to check at least two consecutive blinking cycles. 2

The outdoor unit is abnormal.

Check the blinking pattern, and confirm the abnormal point with the outdoor unit failure mode table. (Refer to outdoor unit service manual.) Make sure to check at least two consecutive blinking cycles. 3

Releasing the failure mode recall function

Release the failure mode recall function by the following procedures.

Turn OFF the power supply and turn it ON again.

Press RESET button of the remote controller.

Repair the defective parts.

Deleting the memorized abnormal condition

After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above.

Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.

Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.

NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.

2.If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.

2.Blinking pattern when the indoor unit is abnormal:

 

 

 

 

Blinking at 0.5-

 

 

 

 

 

 

 

 

Blinking at 0.5-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5-second OFF

second interval

2.5-second OFF second interval

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Beeps

 

 

 

 

 

 

 

 

 

 

 

 

 

Beeps

 

 

 

Beeps

 

 

 

 

 

 

 

 

 

 

 

 

 

Repeated cycle

 

 

 

 

 

Repeated cycle

Repeated cycle

 

 

 

 

 

 

 

 

 

 

3.Blinking pattern when the outdoor unit is abnormal:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blinking at 0.5-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blinking at 0.5-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5-second OFF

 

 

3-second ON

 

 

second interval

 

 

 

2.5-second OFF

3-second ON

 

second interval

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No beep

 

 

 

 

 

Beeps

 

 

 

 

 

 

 

 

No beep

 

 

 

Beeps

 

 

 

 

 

 

Repeated cycle

 

 

 

 

 

 

 

 

Repeated cycle

 

 

 

 

 

 

 

 

 

Repeated cycle