Vulcan-Hart BVD34FP30(F,L)N-1 Installation Cont, Combustible Surround Installation

Models: BVD34FP30(F,L)N-1 BVD36FP32(F,L)N-1 BVD36FP52(F,L)N-1 BVP42FP32(F,L)N-1 BVD34FP50(F,L)N-1 BVP42FP52(F,L)N-1

1 40
Download 40 pages 38.56 Kb
Page 11
Image 11
INSTALLATION (CONT)

INSTALLATION (CONT)

Combustible Surround Installation

Minimum Framing Dimensions

 

BVD34

BVD36

BVP42

"A"

35 3/4"

37 3/4"

37 3/4"

 

(908mm)

(959mm)

(959mm)

"B"

37 3/8"

39 3/8"

43 3/8"

 

(949mm)

(1,000mm)

(1,102mm)

"C"

14 3/8"

17 7/8"

17 7/8"

 

(378mm)

(454mm)

(454mm)

Note: Dimension "C" is the minimum with the fireplace face extending 1/2" in front of the framing to allow for finishing materials.

2 X 4 HEADER

STAND OFF

MANTELSHELF

COMBUSTIBLE SURROUND

FINISHED WALL

FRONT TRIM OR NON-COMBUSTIBLE MATERIAL MAY OVERLAP BLACK PAINTED FACE (INSTALLATION IS OPTIONAL)

JOINT BETWEEN FINISHED WALL AND UNIT SEALED WITH 300° F 149° C SEALANT MATERIAL (SEALANT IS OPTIONAL)

Figure 11

Attention: Add 3-3/4" to “A” dimensions when using a flush mantel base.

Attention: If a base or mantel is not used and the appliance is installed directly on carpeting, tile or other combustible material other than wood flooring, it shall be installed on a metal or wood panel extending the full width and depth of the appliance. The vertical dimension in Figure 11 must be adjusted when a metal or wood panel is placed beneath the appliance.

Finishing (Figure 12)

Finish the walls with the material of your choice. Only non- combustible materials may be used to cover the black fireplace front.

Warning: When finishing the fireplace never obstruct or modify the air inlet/outlet louvers in any manner. Provide adequate clearances around air openings into the combustion chamber.

Caution: If the joints between the finished wall and the fireplace surround (top and sides) are sealed, a 300°F minimum sealant material must be used. These joints are not required to be sealed. Only non-combustible material (using 300°F minimum adhesive if needed), can be applied as facing to the fireplace surround.

Figure 12

Attention: Cold climate installation recommendation: When installing this unit against a non-insulated exterior wall, it is recommended that the outer walls be insulated to conform to applicable insulation codes.

19400-3-0406

Page 11

Page 11
Image 11
Vulcan-Hart BVD34FP30(F,L)N-1, BVP42FP52(F,L)N-1 Installation Cont, Combustible Surround Installation, Finishing Figure