York BP120 Physical Data, Factory Installed Options, Field Installed Accessories, Component

Models: BP120 BP 090

1 44
Download 44 pages 45.17 Kb
Page 19
Image 19
TABLE 10: PHYSICAL DATA

66307-YIM-B-0606

TABLE 10: PHYSICAL DATA

 

Component

Models

 

 

 

 

090

120

 

 

 

 

 

 

Evaporator

Blower, Centrifugal Dia. X Wd. in. (Dia. X Wd. mm)

15 x 15 (381 x 381)

15 x 15 (381 x 381)

 

 

 

Motor, Standard HP (kW)

1-1/2 (1.1)

2 (1.5)

Blower

 

 

 

 

Motor, Optional HP (kW)

2 (1.5)

4 (3)

 

 

 

 

 

Rows

3

4

 

 

 

 

Evaporator Coil

Fins per Inch (2.54 cm.)

15

15

 

 

 

Height in. (mm)

40 (1020)

40 (1020)

 

 

 

 

 

 

Face Area ft.2 each (m2)

13.2 (1.23)

13.2 (1.23)

Condenser Fan

Propeller Dia. in., each (mm)

24 (610)

24 (610)

 

 

 

Motor HP, each (kW)

3/4 (.56)

3/4 (.56)

(2 per Unit)

 

 

 

 

CFM, Nominal (each)

4000

4000

 

 

 

 

 

Rows (each)

1

2

 

 

 

 

Condenser Coil

Fins per Inch (2.54 cm)

20

20

 

 

 

(2 per unit)

Height in., each (mm)

44 (1120)

44 (1120)

 

 

 

 

 

Face Area ft.2 each (mm)

14.5 (1.35)

14.5 (1.35)

Refrigerant

System 1 lb./oz. (kg)

9 lbs. 4 oz. (4.20)

15 lbs. 4 oz. (6.92)

Charge

 

 

 

System 2 lb./oz. (kg)

9 lbs. 0 oz. (4.06)

15 lbs. 0 oz. (6.80)

 

 

 

 

Compressors

Quantity

2

2

 

 

 

Type

Recip

Scroll

 

 

 

 

 

 

Size Wd. x Ht. x Thickness in. (Wd. x Ht x Thickness

25x20x2

25x20x2

Air Filters

mm)

(635 x 508 x 51)

(635 x 508 x 51)

 

Number Per Unit

4

4

 

 

 

 

FACTORY INSTALLED OPTIONS/

FIELD INSTALLED ACCESSORIES

ELECTRIC HEAT ACCESSORY

Electric heaters are available as field installed accessories. Refer to electric heat instructions for installation. These heat- ers mount in the heat compartment with the heating elements extending into the supply air chamber. All electric heaters are fused and intended for use with single point power supply.

ELECTRIC HEAT OPTION

The factory-installed heaters are wired for single point power supply. Power supply need only be brought into the single point terminal block.

These CSA approved heaters are located within the central compartment of the unit with the heater elements extending into the supply air chamber.

Fuses are supplied, where required, by the factory. Some kW sizes require fuses and other do not. Refer to Table 11 for minimum CFM limitations and to Tables 8 and 9 for electrical data.