York DJ150 Unit Weights, 4 POINT LOAD WEIGHT, Clearances, 6 POINT LOAD WEIGHT, UNIT 6 POINT LOAD

Models: DJ150

1 52
Download 52 pages 10.45 Kb
Page 12
Image 12
TABLE 3: UNIT WEIGHTS

035-19046-002-B-0104

TABLE 3: UNIT WEIGHTS

Model DJ150

Shipping

Operating

Weight (lb.)

Weight (lb.)

 

 

 

 

Cooling Unit Only

1415

1400

 

 

 

w/Economizer

85

84

 

 

 

w/Power Exhaust

150

148

 

 

 

w/Gas Heat*

110

110

w/Electric Heat

49

49

*. 8 Tube Heat Exchanger

†.54 kW heater

TABLE 4: 4 POINT LOAD WEIGHT

Model

 

Location (lbs.)*

 

 

 

 

 

 

A

B

C

D

 

 

 

 

 

DJ150

282

323

424

371

 

 

 

 

 

*. Weights include largest gas heat option.

CLEARANCES

All units require particular clearances for proper operation and service. Installer must make provisions for adequate combustion and ventilation air in accordance with section 5.3 of Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 – Latest Edition (in U.S.A.), or Sections 7.2, 7.3, or 7.4 of Gas Installation Codes, CSA-B149.1 (in Canada) - Latest Edition, and/or applicable provisions of the local building codes. Refer to Table 6 for clearances required for combustible construction, servicing, and proper unit oper- ation.

Do not permit overhanging structures or shrubs to obstruct condenser air discharge outlet, combustion air inlet or vent outlets.

TABLE 5: 6 POINT LOAD WEIGHT

Model

 

 

Location (lbs.)*

 

 

 

 

 

 

 

 

 

A

B

C

D

E

F

 

 

 

 

 

 

 

DJ150

184

201

220

289

264

242

 

 

 

 

 

 

 

*. Weights include largest gas heat option.

 

LEFT

 

 

 

 

FRONT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

D

 

 

 

 

 

 

 

 

 

 

 

 

A

 

B

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F

 

 

 

FIGURE 5 - UNIT 6 POINT LOAD

Excessive exposure to contaminated combustion air will result in safety and performance related prob- lems. To maintain combustion air quality, the recom- mended source of combustion air is the outdoor air supply. The outdoor air supplied for combustion should be free from contaminants due to chemical exposure that may be present from the following sources.

Commercial buildings

Indoor pools

Laundry rooms

Hobby or craft rooms

Chemical storage areas

The following substances should be avoided to maintain outdoor combustion air quality.

Permanent wave solutions

• Chlorinated waxes and cleaners

• Chlorine based swimming pool cleaners

Water softening chemicals

De-icing salts or chemicals

Carbon tetrachloride

Halogen type refrigerants

• Cleaning solvents (such as perchloroethylene)

47-½"

LEFT

25-½"

FRONT

• Printing inks, paint removers, varnishes, etc.

Hydrochloric acid

Cements and glues

Anti-static fabric softeners for clothes dryers

• Masonry acid washing materials

FIGURE 6 - UNIT CENTER OF GRAVITY

12

Unitary Products Group

Page 12
Image 12