York DJ150 installation manual Unit Dimensions, Detail C, Detail A, Unit Clearances, Detail B

Models: DJ150

1 52
Download 52 pages 10.45 Kb
Page 13
Image 13
FIGURE 7 - UNIT DIMENSIONS

035-19046-002-B-0104

119-7/16

30-11/32

Power

50-3/4Entry

2-1/2

4-1/4

Control

Entry 7/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17-3/16

 

 

 

3

0-3/16

 

59

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

4-3/1

6

6-3/16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEFT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIGURE 7 - UNIT DIMENSIONS

DETAIL A

 

 

 

 

GasPipeInlet

 

 

 

 

 

 

 

 

 

5-1/4

 

 

 

 

 

Base

 

 

 

 

 

 

 

 

 

 

 

17-13/16

 

Pan

 

 

 

 

 

 

 

 

 

 

ViewofWalAcrossfromCoil

 

 

TABLE 6:

UNIT CLEARANCES

 

 

Top*

 

 

 

72”

 

Right

 

12”

Front

 

 

 

36”

 

Left

 

36”

Rear

 

 

 

36”

 

Bottom**

 

0”

*. Units must be installed outdoors. Overhanging struc- ture or shrubs should not obstruct condenser air dis- charge outlet.

†.The products of combustion must not be allowed to accumulate within a confined space and re-circulate.

‡.To remove the slide-out drain pan, a rear clearance of sixty inches is required. If space is unavailable, the drain pan can be removed through the front by separat- ing the corner wall.

**. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.

NOTE: A one-inch clearance must be provided between any combustible material and the supply ductwork for a distance of 3 feet from the unit.

See Detail A

Con-

venience

Outlet

 

 

 

 

11-1/2

 

Con-

 

 

 

 

 

venience

 

 

 

 

 

Outlet

 

 

 

 

 

Power

 

 

 

 

 

Entry

 

FRONT

 

 

 

7/8

 

 

For

 

 

 

 

 

 

 

Baserail

 

For Drain Dimensions

 

Dimensions

 

 

 

 

 

 

See Detail C

 

 

See

 

 

 

 

Detail B

89

27

DETAIL B

2-3/8

 

3-3/4

3-9/16

DETAIL C

5-3/8

NOTE: If the unit includes gas heating, locate the unit so the flue exhaust is at least:

Three (3) feet above any forced air inlet located within 10 horizontal feet (excluding those integral to the unit).

Four (4) feet below, four (4) horizontal feet from, or one

(1) foot above any door or gravity air inlet into the build- ing.

Four (4) feet from electric meters, gas meters, regula- tors, and relief equipment.