York DJ150 Adjustment Of Temperature Rise, Burners/Orifices Inspection/Servicing

Models: DJ150

1 52
Download 52 pages 10.45 Kb
Page 42
Image 42
ADJUSTMENT OF TEMPERATURE RISE

035-19046-002-B-0104

EXAMPLE:

By actual measurement, it takes 19 seconds for the hand on a 1 cubic foot dial to make a revolution with a 192,000 Btuh furnace running. To determine rotations per minute, divide 60 by 19 = 3.16. To calculate rotations per hour, multiply 3.16 60 = 189.6. Multiply 189.6 1 (0.5 if using a 1/2 cubic foot dial) = 189.6. Multiply 189.6 (the Btu rating of the gas). For this example, assume the gas has a Btu rating of 1050 Btu/ft.3. The result of 199,000 Btuh is within 5% of the 192,000 Btuh rating of the furnace.

ADJUSTMENT OF TEMPERATURE RISE

The temperature rise (the difference of temperature between the return air and the heated air from the furnace) must lie within the range shown on the CSA rating plate and the data in Table 25.

After the temperature rise has been determined, the CFM can be calculated as follows:

CFM = Btu Input

0.8

(-----------------------------1.08⋅ ∆°F)

After about 20 minutes of operation, determine the furnace temperature rise. Take readings of both the return air and the heated air in the ducts (about 6 feet from the furnace) where they will not be affected by radiant heat. Increase the blower CFM to decrease the temperature rise; decrease the blower CFM to increase the rise (See ’SUPPLY AIR DRIVE ADJUSTMENT’).

NOTE: Each gas heat exchanger size has a minimum allowable CFM. Below this CFM, the limit will open below this rating.

BURNERS/ORIFICES INSPECTION/SERVICING

Before checking or changing burners, pilot or orifices,

CLOSE MAIN MANUAL SHUT-OFF VALVE AND SHUT OFF ALL POWER TO THE UNIT.

1.Open the union fitting just upstream of the unit gas valve and downstream from the main manual shut-off valve in the gas supply line.

2.Remove the screws holding each end of the manifold to the manifold supports.

3.Disconnect wiring to the gas valves and spark igniter(s). Remove the manifold & gas valve assembly. Orifices can now be inspected and/or replaced.

To service burners, complete step 4.

4.Remove the heat shield on top of the manifold supports. Burners are now accessible for inspection and/or replacement.

NOTE: Reverse the above procedure to replace the assem- blies.

Make sure that burners are level and seat at the rear of the gas orifice.

HIGH&LOW GASADJUSTMENT

LO

HI

ON

INLET

 

PRESSURE

OFF

 

TAP

OUTLET

 

 

PRESSURE

MATE-N-LOCK TAP

CONNECTORS

MV

CBURNERS/ORIFICES INSPECTION/SERVICING

HI FIGURE 27 - TYPICAL GAS VALVE

FIGURE 27 - TYPICAL GAS VALVE

42

Unitary Products Group

Page 42
Image 42
York DJ150 installation manual Adjustment Of Temperature Rise, Burners/Orifices Inspection/Servicing, Typical Gas Valve