FIGURE 2 - COMPRESSOR SECTION

035-19046-002-B-0104

2.Turn each bracket toward the ground and the protective plywood covering will drop to the ground.

3.Remove the condenser coil external protective covering prior to operation.

4.Remove the toolless doorknobs and instruction packet prior to installation.

Toolless

Doorknobs

Installation

Instruction

Packet

FIGURE 2 - COMPRESSOR SECTION

This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state and national codes including, but not limited to, building, electrical, and mechani- cal codes.

The furnace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing at pressures in excess of 1/2 PSIG.

Pressures greater than 1/2 PSIG will cause gas valve damage resulting in a hazardous condition. If it is subjected to a pressure greater than 1/2 PSIG, the gas valve must be replaced.

The furnace must be isolated from the gas supply piping system by closing its individual manual shut- off valve during any pressure testing of the gas sup- ply piping system at test pressures equal to or less than 1/2 PSIG.

LIMITATIONS

These units must be installed in accordance with the follow- ing:

In U.S.A.:

1.National Electrical Code, ANSI/NFPA No. 70 - Latest Edition

2.National Fuel Gas Code, ANSI Z223.1 - Latest Edition

3.Gas-Fired Central Furnace Standard, ANSI Z21.47a. - Latest Edition

4.Local building codes, and

5.Local gas utility requirements

In Canada:

1.Canadian Electrical Code, CSA C22.1

2.Installation Codes, CSA - B149.1.

3.Local plumbing and waste water codes, and

4.Other applicable local codes.

Refer to Tables 1 & 2 for unit application data.

After installation, gas fired units must be adjusted to obtain a temperature rise within the range specified on the unit rating plate.

If components are to be added to a unit to meet local codes, they are to be installed at the dealer’s and/or customer’s expense.

Size of unit for proposed installation should be based on heat loss/heat gain calculation made according to the methods of Air Conditioning Contractors of America (ACCA).

This furnace is not to be used for temporary heating of build- ings or structures under construction.