York DJ150 installation manual Supply

Models: DJ150

1 52
Download 52 pages 10.45 Kb
Page 21
Image 21
Supply

035-19046-002-B-0104

TABLE 8: ELECTRICAL DATA DJ150 (12-1/2 TON) WITHOUT POWERED CONVENIENCE OUTLET

 

 

 

 

Supply

Pwr

Pwr

 

 

 

Min. Circuit

MCA

Max

Max Fuse* Size

 

 

 

OD Fan

 

 

 

w/Power

Fuse*

w/Power

 

Compressors

Blower

Exh

Conv

Electric Heater

Actual

Heater

Ampacity

Voltage

 

 

Motors

Motor FLA

Motor

Outlet

(Amps)

Exhaust

Size

Exhaust

 

 

 

 

 

 

 

 

Model No.

KW

Amps

 

 

(Amps)

(Amps)

(Amps)

 

RLA

LRA

FLA

3

5

FLA

FLA

 

 

 

3

5

3

5

3

5

3

5

 

ea.

ea.

ea.

HP

HP

 

 

 

HP

HP

HP

HP

HP

HP

HP

HP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

None

--

--

61.9

67.1

67.4

72.6

80

80

80

90

 

 

 

 

 

 

 

 

2TP04521825

13.5

37.5

61.9

67.1

67.4

73.8

80

80

80

90

208

20.0

146.0

1.5

10.9

16.1

5.5

0.0

2TP04522425

18.0

50.0

76.1

82.6

83.0

89.5

80

90

90

90

 

 

 

 

 

 

 

 

2TP04523625

25.5

70.8

102.1

108.6

109.0

115.5

110

110

110

125

 

 

 

 

 

 

 

 

2TP04525425

40.6

112.7

154.5

161.0

161.4

167.9

175

175

175

175

 

 

 

 

 

 

 

 

None

--

--

61.9

67.1

67.4

72.6

80

80

80

90

 

 

 

 

 

 

 

 

2TP04521825

18.0

43.3

67.8

74.3

74.6

81.1

80

80

80

90

230

20.0

146.0

1.5

10.9

16.1

5.5

0.0

2TP04522425

24.0

57.7

85.8

92.3

92.7

99.2

90

100

100

100

 

 

 

 

 

 

 

 

2TP04523625

34.0

81.8

115.9

122.4

122.7

129.2

125

125

125

150

 

 

 

 

 

 

 

 

2TP04525425

54.0

129.9

143.5

150.0

150.4

156.9

175

175

175

175

 

 

 

 

 

 

 

 

None

--

--

27.4

30.2

29.6

32.4

35

35

35

40

 

 

 

 

 

 

 

 

2TP04521846

18

22.6

33.7

37.2

36.4

39.9

35

40

40

40

460

8.4

73.0

0.8

5.3

8.1

2.2

0.0

2TP04522446

24

30.1

42.7

46.2

45.5

49

45

50

50

50

 

 

 

 

 

 

 

 

2TP04523646

34

42.7

57.7

61.2

60.5

64

60

70

70

70

 

 

 

 

 

 

 

 

2TP04525446

54

67.8

71.6

75.1

74.3

77.8

80

90

80

90

 

 

 

 

 

 

 

 

None

--

--

21.6

23.5

23.4

25.3

25

30

30

30

 

 

 

 

 

 

 

 

2TP04521858

18

18.1

26.8

29.2

29

31.4

30

30

30

35

575

6.7

60.0

0.6

4.1

6.0

1.8

0.0

2TP04522458

24

24.1

34

36.4

36.2

38.6

35

40

40

40

 

 

 

 

 

 

 

 

2TP04523658

34

34.1

46

48.4

48.3

50.6

50

50

50

60

 

 

 

 

 

 

 

 

2TP04525458

54

54.2

57.1

59.5

59.3

61.7

70

70

70

70

*Maximum HACR breaker of the same AMP size is applicable.

TABLE 9: ELECTRICAL DATA DJ150 (12-1/2 TON) WITH POWERED CONVENIENCE OUTLET

 

 

 

 

Supply

Pwr

Pwr

 

 

 

Min. Circuit

MCA

Max

Max Fuse* Size

 

 

 

OD Fan

 

 

 

w/Power

Fuse*

w/Power

 

Compressors

Blower

Exh

Conv

Electric Heater

Actual

Heater

Ampacity

Voltage

 

 

Motors

Motor FLA

Motor

Outlet

(Amps)

Exhaust

Size

Exhaust

 

 

 

 

 

 

 

 

Model No.

KW

Amps

 

 

(Amps)

(Amps)

(Amps)

 

RLA

LRA

FLA

3

5

FLA

FLA

 

 

 

3

5

3

5

3

5

3

5

 

ea.

ea.

ea.

HP

HP

 

 

 

HP

HP

HP

HP

HP

HP

HP

HP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

None

--

--

71.9

77.1

77.4

82.6

90

90

90

100

 

 

 

 

 

 

 

 

2TP04521825

13.5

37.5

73.0

79.5

79.8

86.3

90

90

90

100

208

20.0

146.0

1.5

10.9

16.1

5.5

10.0

2TP04522425

18.0

50.0

88.6

95.1

95.5

102.0

90

100

100

110

 

 

 

 

 

 

 

 

2TP04523625

25.5

70.8

114.6

121.1

121.5

128.0

125

125

125

150

 

 

 

 

 

 

 

 

2TP04525425

40.6

112.7

167.0

173.5

173.9

180.4

175

175

175

200

 

 

 

 

 

 

 

 

None

--

--

71.9

77.1

77.4

82.6

90

90

90

100

 

 

 

 

 

 

 

 

2TP04521825

18.0

43.3

80.3

86.8

87.1

93.6

90

90

90

100

230

20.0

146.0

1.5

10.9

16.1

5.5

10.0

2TP04522425

24.0

57.7

98.3

104.8

105.2

111.7

100

110

110

125

 

 

 

 

 

 

 

 

2TP04523625

34.0

81.8

128.4

134.9

135.2

141.7

150

150

150

150

 

 

 

 

 

 

 

 

2TP04525425

54.0

129.9

156.0

162.5

162.9

169.4

175

175

175

175

 

 

 

 

 

 

 

 

None

--

--

32.4

35.2

34.6

37.4

40

40

40

45

 

 

 

 

 

 

 

 

2TP04521846

18

22.6

39.9

43.4

42.7

46.2

40

45

45

50

460

8.4

73.0

0.8

5.3

8.1

2.2

5.0

2TP04522446

24

30.1

49

52.5

51.7

55.2

50

60

60

60

 

 

 

 

 

 

 

 

2TP04523646

34

42.7

64

67.5

66.7

70.2

70

70

70

80

 

 

 

 

 

 

 

 

2TP04525446

54

67.8

77.8

81.3

80.6

84.1

90

90

90

90

 

 

 

 

 

 

 

 

None

--

--

25.6

27.5

27.4

29.3

30

30

30

35

 

 

 

 

 

 

 

 

2TP04521858

18

18.1

31.8

34.2

34

36.4

35

35

35

40

575

6.7

60.0

0.6

4.1

6.0

1.8

4.0

2TP04522458

24

24.1

39

41.4

41.2

43.6

40

45

45

45

 

 

 

 

 

 

 

 

2TP04523658

34

34.1

51

53.4

53.3

55.6

60

60

60

60

 

 

 

 

 

 

 

 

2TP04525458

54

54.2

62.1

64.5

64.3

66.7

70

70

70

70

*Maximum HACR breaker of the same AMP size is applicable.