15.DO NOT use gaskets on covers of explosion-proof type boxes. The sealing compound found around wires at all junction box entrances is a requirement of the National Electrical Code and should not be disturbed. Tighten junction box covers before replacing panels.
16.DO NOT use knock-out boxes or flexible conduit for installing this unit. All power and lighting wires should be run in threaded, rigid, metal conduit. All threaded connections must be drawn up tight with five (5) threads minimum engagement. Only one opening in the AC junction box is provided. At completion of the installation, it is the installer's responsibility to ensure that any unused openings are plugged.
SUPPLY LINE - UNDERGROUND TANKS
If you are using an underground tank, pitch the tank away from suction end. Horizontal runs of suction line should slope down from the pump toward the tank. Do not exceed an equivalent lift of 12' for gasoline or 14' for diesel to the center line of the pumping unit, including friction resistance in the suction pipe.
The end of the suction pipe must be at least three inches from bottom of tank.
The tank or piping should not be located under traffic areas. Swing joints (two ells) will prevent damage to piping due to frost heave or ground settlement.
Use nonhardening, gasoline-resistant pipe compound on male threads of all pipe joints for liquid handling piping.