Raypak P-4001, P-1826, P-926, P-2100 manual

Page 13
2.Lace metal strapping or clamps, (NOT PROVID- ED) through the ¾” slots on the cover and fasten securely to pipe as shown in Fig. 15 & 16. Do not over-tighten clamps.

Fig. 13: Poolstat Control

Fig. 14: Control Cover

2.Lace metal strapping or clamps, (NOT PROVID- ED) through the ¾” slots on the cover and fasten securely to pipe as shown in Fig. 15 & 16. Do not over-tighten clamps.

3.Remove either the left or right “knock-out” for wiring on the poolstat control as shown in Fig. 17.

Fig. 17: Remove Knockout

4.Attach appropriate conduit and connectors to the poolstat control.

5.Attach wires to the poolstat wire terminals. See Fig. 18.

Fig. 15: Hose Clamp Slots

Fig. 16: Insert Clamps

Fig. 18: Attach Wires

6.Install poolstat control to the cover and fasten cover screws.

7.Poolstat should be mounted level as shown in Fig. 19.

Fig. 19: Mount Level

13

Image 13
Contents Raytherm Commercial Swimming Pool Heater INSTALLATION & OPERATING INSTRUCTIONSModels P-926to P-1826 & P-2100to P-4001 Corrosive water voids all warranties CONTENTS Pay Attention to These Terms WARNINGSDANGER GENERAL SPECIFICATIONS RECEIVING EQUIPMENT INSTALLATIONBase Installation Code RequirementsCombustion Air Indoor Units Only ClearancesIndoor Heaters Outdoor HeatersDrafthood Indoor Models Venting ConnectionsVent Piping Gas Pressure Regulator Gas Supply ConnectionsModel Venting of Diaphragm Gas Components1-1/4” 1-1/2”CONTROLS Flow SwitchWater Connections Automatic Chlorinators and Chemical Feeders Water Pressure SwitchUnitherm Governor Operation Companion Flange Connections ModelsConnection Model NoMinimum Model No. Loop* Flow Rates Heater Flow2.Lace metal strapping or clamps, NOT PROVID- ED through the ¾” slots on the cover and fasten securely to pipe as shown in Fig. 15 & 16. Do not over-tightenclamps HEATER Models 0926 thru 1223 with UG ISOLATION VALVESFORSERVICE RECOMMENDED FIELD INSTALLEDBLENDEDWATER TEMPERATURE THERMOMETERATHEATERINLETHEATEROUTLETTEMPERATURETHERMOMETER Models 2100 thruAuxiliary Bypass Valve Adjustment External Auxiliary Bypass Valve Where Required926-1223Models Only Temperature ControlsHigh & Low Gas Pressure Switches Electrical WiringLow Water Cutoff Electronic IgnitionWiring Diagram-Models Wiring Diagram-Models Wiring Diagram-Models Wiring Diagram-Models Pressure Switch Adjustment Pressure SwitchSERVICING General Location Of ControlsPilot Safety START-UP PROCEDURESTwo-SpeedPumps Before Start-UpAfter Start-Up INSPECTION PROCEDURESBurners Tube Cleaning Procedure Typical SERVICING PROCEDURESBurner Drawer Removal Gas Valve RemovalHeat Exchanger Reassembly Pilot Removal and CleaningMain Burner and Orifice Removal Heat Exchanger RemovalTube Replacement Procedure Control Well ReplacementProcedure For Cleaning Flue Gas Passageways Combustion Chamber RemovalUnitherm Governor Replacement MAINTENANCE AND CAREUNITHERM GOVERNOR WITH POWER ELEMENT INLET/OUTLET HEADER OUTLET INLET GASKETWinterizing Your Heater MECHANICAL FOR QUALIFIED SERVICE PERSONNEL ONLY TROUBLESHOOTINGIMPORTANT NOTICE Reset time clock or refer to heater sizing chartClean filter Refer to installation instructionsIntermittent Pilot System TROUBLESHOOTING HONEYWELL S8600ELECTRICAL ELECTRONIC IGNITION IID IID STARTHEAT EXCHANGER WARRANTY LIMITED WARRANTY RAYTHERM TYPE P SIZESADDITIONAL WARRANTY EXCLUSIONS PARTS REPLACEMENT