SERVICING
General Location Of Controls
Models
Inlet/Outlet | Pressure |
Header | Switch |
Unitherm | Electrical |
Governor | Conn. |
| |
control/ |
|
Temp. Control | Main Burner Gas Valve |
Fig. 28: General Location of Controls
(Models
Models
Inlet/Outlet
Header w/Bypass
Pump
Electrical
Connection
| Main | Burner |
Manual On/Off Valve | Gas | Valve |
Fig. 29: General Location of Controls
(Models
Temperature Control
The pool water temperature is controlled by the pool thermostat. The heater water temperature high limit is controlled by the manual reset high limit.
Pressure Switch
The pressure switch, or heater actuator on Models
Pressure Switch Adjustment
1.Make sure the pool filter is clean before adjusting the switch.
2.Set the heater control to the OFF mode.
3.Turn the filter pump on and confirm that the pres- sure switch is closed (use a multimeter to check). If the pressure switch fails to close, either the switch setting is too high or the filter pump is not supplying enough pressure.
4.Turn the heater ON.
5.Manually turn the pressure adjustment knob clock- wise until the heater shuts off. (A flat screw driver may be necessary if knob is too tight).
6.Slowly turn the adjustment knob
7.Turn an additional 1/2 turn
8.While the heater is running, check the adjustment by turning the pump off and on several times. The burners should shut off immediately when the pump is turned off. If it does not, repeat the above steps until proper operation is observed.
24