Raypak P-1826, P-4001, P-926, P-2100 manual Gas Supply Connections, Gas Pressure Regulator

Page 8
Gas Supply Connections

At the time of removal of an existing heater, the follow- ing steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remain- ing connected to the common venting system are not in operation.

(a)Seal any unused openings in the common venting system.

(b)Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

(c)Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the com- mon venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will oper- ate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.

(d)Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.

(e)Test for spillage at the drafthood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a ciga- rette, cigar or pipe.

(f)After it has been determined that each appliance remaining connected to the common venting sys- tem properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.

(g)Any improper operation of the common venting system should be corrected so the installation conforms with the latest edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54. When re- sizing any portion of the common venting system, the common venting system should be re-sized to approach the minimum size as determined using the appropriate tables in the National Fuel Gas Code, ANSI Z223.1/ NFPA 54.

For special venting applications that require reduced vent sizes and through the wall venting, the optional D Series Power Vent can be used. Consult the factory or your local Raypak representative.

8

Gas Supply Connections

Gas piping must have a sediment trap ahead of the heater gas controls, and a manual shut-off valve locat- ed outside the heater jacket. All gas piping should be tested after installation in accordance with local codes.

MANUAL

SHUT-OFF

VALVE

SEDIMENT Gas Pressure Regulator

TRAP

Fig. 5: Gas Piping

CAUTION: The heater and its manual shut-off valve must be disconnected from the gas supply during any pressure testing of that system at test pressures in excess of 1/2 psig (3.45 KPA). Dissipate test pressure in the gas supply line before reconnecting the heater and its manual shut-off valve to gas supply line. FAILURE TO FOLLOW THIS PROCEDURE MAY DAMAGE THE GAS VALVE. OVER PRESSURIZED GAS VALVES ARE NOT COVERED BY WARRANTY.The heater and its gas connections shall be leak tested before placing the appliance in operation. Use soapy water for leak test. DO NOT use open flame.

CAUTION: Do not use Teflon tape on gas line pipe thread. A pipe compound rated for use with natural and propane gases is recommended. Apply sparingly only on male pipe ends, leaving the two end threads bare.

A minimum of 7 in. WC and a maximum of 10.5 in. WC upstream pressure under load, and no load conditions must be provided for natural gas or a minimum of 11 in. WC and a maximum of 13 in. WC for propane gas.

Gas Pressure Regulator

The gas pressure regulator is preset and sealed at 4 in. WC for natural gas, and 11 in. WC for propane gas. Between the gas valve and the burners is a 1/8" pipe plug. The pressure at this point, taken with a manome- ter, should be about 3.7 in. WC natural gas and 10.5 in. WC propane gas. If an adjustment is needed, remove seal and turn adjustment screw clockwise

, to increase pressure or counter-clockwise Manual background, to decrease pressure.

Image 8
Contents Models P-926to P-1826 & P-2100to P-4001 INSTALLATION & OPERATING INSTRUCTIONSRaytherm Commercial Swimming Pool Heater Corrosive water voids all warranties CONTENTS DANGER WARNINGSPay Attention to These Terms RECEIVING EQUIPMENT INSTALLATION GENERAL SPECIFICATIONSBase Installation Code RequirementsClearances Combustion Air Indoor Units OnlyIndoor Heaters Outdoor HeatersVent Piping Venting ConnectionsDrafthood Indoor Models Gas Supply Connections Gas Pressure RegulatorVenting of Diaphragm Gas Components Model1-1/4” 1-1/2”Water Connections Flow SwitchCONTROLS Water Pressure Switch Automatic Chlorinators and Chemical FeedersUnitherm Governor Operation Companion Flange Connections ModelsModel No ConnectionMinimum Model No. Loop* Flow Rates Heater Flow2.Lace metal strapping or clamps, NOT PROVID- ED through the ¾” slots on the cover and fasten securely to pipe as shown in Fig. 15 & 16. Do not over-tightenclamps HEATER Models 0926 thru 1223 with UG RECOMMENDED FIELD INSTALLED ISOLATION VALVESFORSERVICEBLENDEDWATER TEMPERATURE THERMOMETERATHEATERINLETModels 2100 thru HEATEROUTLETTEMPERATURETHERMOMETERExternal Auxiliary Bypass Valve Where Required Auxiliary Bypass Valve Adjustment926-1223Models Only Temperature ControlsElectrical Wiring High & Low Gas Pressure SwitchesLow Water Cutoff Electronic IgnitionWiring Diagram-Models Wiring Diagram-Models Wiring Diagram-Models Wiring Diagram-Models Pressure Switch Pressure Switch AdjustmentSERVICING General Location Of ControlsSTART-UP PROCEDURES Pilot SafetyTwo-SpeedPumps Before Start-UpBurners INSPECTION PROCEDURESAfter Start-Up SERVICING PROCEDURES Tube Cleaning Procedure TypicalBurner Drawer Removal Gas Valve RemovalPilot Removal and Cleaning Heat Exchanger ReassemblyMain Burner and Orifice Removal Heat Exchanger RemovalControl Well Replacement Tube Replacement ProcedureProcedure For Cleaning Flue Gas Passageways Combustion Chamber RemovalMAINTENANCE AND CARE Unitherm Governor ReplacementUNITHERM GOVERNOR WITH POWER ELEMENT INLET/OUTLET HEADER OUTLET INLET GASKETWinterizing Your Heater IMPORTANT NOTICE TROUBLESHOOTINGMECHANICAL FOR QUALIFIED SERVICE PERSONNEL ONLY or refer to heater sizing chart Reset time clockClean filter Refer to installation instructionsTROUBLESHOOTING HONEYWELL S8600 Intermittent Pilot SystemELECTRICAL ELECTRONIC IGNITION IID IID STARTLIMITED WARRANTY RAYTHERM TYPE P SIZES HEAT EXCHANGER WARRANTYADDITIONAL WARRANTY EXCLUSIONS PARTS REPLACEMENT