STANDBY PERMANENT - MOUNT SERIES GENERATOR

ELECTRICAL CONNECTION INFORMATION

High voltage may be present at receptacles and load studs while engine is operating - DANGER of electrical shock is present. Use extreme care.

Voltage is present at the 120V/15 Amp convenience receptacle only when generator is operating.

When configured for 277/480 main output, these receptacles Will be delivering 139 VAC. Disconnection to avoid possible equipment damage is suggested.

HARD WIRE LOAD TERMINAL BLOCK

1.Voltage available at load block is outlined in a chart below.

2.Cables must be brought into load block cabinet.

3.Do not start engine with load turned "on". Allow engine to come up to speed and warm up first.

 

AVAILABLE VOLTAGE:

CONNECTION OF

 

GENERATOR LEADS

STUD

120/240

4 LEAD

1-2 = 240 VAC, 1 Phase

 

 

1-N, 2-N = 120 VAC, 1 Phase

277/480

High Wye

1-2-3 = 480 VAC, 3 Phase

 

 

1-N, 2-N, 3-N = 277 VAC, 1 Phase

120/240

Delta

1-2-3 = 240 VAC, 3 Phase

 

 

2-3 = 240 VAC, 1 Phase

 

 

1-N, 2-N, 3-N = 120 VAC, 1 Phase

120/208

Low Wye

1-2-3 = 208 VAC, 3 phase

 

 

2-3 = 208 VAC, 1 Phase

 

 

1-N, 2-N, 3-N = 120 VAC, 1 Phase

 

 

 

Image 20
Contents Standby Permanent Mount Series Generator Forward Page Page Ż ż for Gasoline or Diesel Powered Generator Sets ż ż ż ż Ż ż for Gasoline or Diesel Powered Generator Sets ż ż ż ż Standby PERMANENT- Mount Series Generator Baldor Generator Features Options BaldorFarm Duty 1-Phase Model DLC25 Engine SpecificationsModel D50 Farm Duty 1-Phase Model DLC50 PowerPACModel D60 Farm Duty 1-Phase Model DLC60 Engine SpecificationsModel D75 Farm Duty 1-Phase Model DLC75 Engine DataModel D100 Farm Duty 1-Phase Model DLC100Model D130 Farm Duty 1-Phase Model DLC130 Hard Wire Load Terminal Block Electrical Connection InformationConnection Information Standby Permanent Mount Series Generator Generator Mounting RequirementsEngine Cooling Requirements Engine Cooling AIR HOT Exhaust Gases Backpressure must not exceed 20 of water columnPage Building Ventilation Generator END Cooling AIRBuilding Ventilation Exhaust Requirements Exhaust PipingExhaust Piping Thru Walls and Roofs Exhaust Thimble Minimum O.DDouble Thimble Roof Outlet Details Control Panel Operation Function Page Page Operation Starting Operation Cranking Control No Voltage LOW VoltageOverheating Fluctuating VoltageHigh Voltage Generator Frame Produces Shock When Touched Mechanical NoiseTroubleshooting Engine Limited Warranty Warranty Period Limitations Distributor Information END User / Owner Information RPMKVA CurrentPre Start-Up Check List Start-Up Procedure Oregon Street Oshkosh WI Phone 920-239-4200 Fax California Proposition 65 Warning Oregon Street Oshkosh WI Phone 920 236-4200 Fax 920