Baldor ISO9001 manual Connection Information

Page 21

CONNECTION INFORMATION

Your new Pow'R Gard Generator has all interconnecting wiring terminated at a junction box. All wiring will be clearly labeled as being load, remote start contacts and AC input terminals and are to be connected as described below.

LOAD - These connections are rated and sized according to the KW of the generator. Proper lead wire from these points to the automatic transfer switch (or load switching device) is mandatory. See enclosed transfer switch information for corresponding generator input terminals.

REMOTE START CONTACTS - This two wire connection, once connected to an appropriate switch, will start the generator and perform as described in the remote start/stop literature. These contacts are connected to the "Engine Start Contacts" of the automatic transfer switch.

A Two Pole connection switch - normally open, closed to operate switch may also be used to start the generator.

AC INPUT - These connections are for units with float type battery chargers or engine block heater combinations. A constant supply of 120 volts AC (or as specified) is needed at these terminals to power these devices.

Power is not required when the unit is in operation. Internal Battery charging and radiant heat during operation eliminate the need for these devices.

It is recommended that units utilizing an automatic transfer switch with adjustable time delays have the initial adjustments made prior to startup.

Factory recommendations are: allow 2 second delay on startup, 15 second delay on emergency to normal.

Image 21
Contents Standby Permanent Mount Series Generator Forward Page Page Ż ż for Gasoline or Diesel Powered Generator Sets ż ż ż ż Ż ż for Gasoline or Diesel Powered Generator Sets ż ż ż ż Standby PERMANENT- Mount Series Generator Baldor Baldor Generator Features OptionsEngine Specifications Farm Duty 1-Phase Model DLC25Model D50 PowerPAC Farm Duty 1-Phase Model DLC50Model D60 Engine Specifications Farm Duty 1-Phase Model DLC60Model D75 Engine Data Farm Duty 1-Phase Model DLC75Model D100 Model DLC100 Farm Duty 1-PhaseModel D130 Farm Duty 1-Phase Model DLC130 Electrical Connection Information Hard Wire Load Terminal BlockConnection Information Generator Mounting Requirements Engine Cooling RequirementsStandby Permanent Mount Series Generator Engine Cooling AIR Backpressure must not exceed 20 of water column HOT Exhaust GasesPage Generator END Cooling AIR Building VentilationBuilding Ventilation Exhaust Piping Exhaust RequirementsExhaust Thimble Minimum O.D Exhaust Piping Thru Walls and RoofsDouble Thimble Roof Outlet Details Control Panel Operation Function Page Page Operation Starting Operation Cranking Control LOW Voltage No VoltageFluctuating Voltage High VoltageOverheating Mechanical Noise Generator Frame Produces Shock When TouchedTroubleshooting Engine Limited Warranty Warranty Period Limitations RPM Distributor Information END User / Owner InformationKVA CurrentPre Start-Up Check List Start-Up Procedure Oregon Street Oshkosh WI Phone 920-239-4200 Fax California Proposition 65 Warning Oregon Street Oshkosh WI Phone 920 236-4200 Fax 920