LOW VOLTAGE (Continued)

CAUSE

CHECK AND REMEDY

High resistance connections-

Make better connection electrically and

Connections will be warm or hot

mechanically.

Shorted field.

Test field coils for possible short by checking

 

resistance with an ohmmeter or resistance bridge.

 

Return rotor assembly to factory for repair if alternator

 

field coils are shorted.

Low power factor

Reduce inductive (motor) load. Some AC motors

 

Draw approximately the same current regardless of

 

load. Do not use motors of larger horsepower rating

 

than is necessary to carry the mechanical load.

FLUCTUATING VOLTAGE

(May be indicated by flickering lights.)

CAUSE

CHECK AND REMEDY

Irregular speed of engine.

Check engine for malfunction or load for fluctuation.

Fluctuating speed.

Stabilize load. The addition of a lamp load (resistance

 

load) may compensate partially for load changes

 

caused by intermittent motor operation. Do not

 

overload.

Loose terminal or load connections.

Make better connection mechanically and electrically.

Defective bearing causing uneven air gap. Replace worn bearing.

 

HIGH VOLTAGE

CAUSE

CHECK AND REMEDY

Excessive speed.

Check engine for malfunction.

 

OVERHEATING

CAUSE

CHECK AND REMEDY

Generator overloaded.

Reduce load. (Check with ammeter and compare with

 

nameplate rating.)

Clogged ventilating screens.

Clean air passages.

Image 38
Contents Standby Permanent Mount Series Generator Forward Page Page Ż ż for Gasoline or Diesel Powered Generator Sets ż ż ż ż Ż ż for Gasoline or Diesel Powered Generator Sets ż ż ż ż Standby PERMANENT- Mount Series Generator Baldor Generator Features Options BaldorFarm Duty 1-Phase Model DLC25 Engine SpecificationsModel D50 Farm Duty 1-Phase Model DLC50 PowerPACModel D60 Farm Duty 1-Phase Model DLC60 Engine SpecificationsModel D75 Farm Duty 1-Phase Model DLC75 Engine DataModel D100 Farm Duty 1-Phase Model DLC100Model D130 Farm Duty 1-Phase Model DLC130 Hard Wire Load Terminal Block Electrical Connection InformationConnection Information Standby Permanent Mount Series Generator Generator Mounting RequirementsEngine Cooling Requirements Engine Cooling AIR HOT Exhaust Gases Backpressure must not exceed 20 of water columnPage Building Ventilation Generator END Cooling AIRBuilding Ventilation Exhaust Requirements Exhaust PipingExhaust Piping Thru Walls and Roofs Exhaust Thimble Minimum O.DDouble Thimble Roof Outlet Details Control Panel Operation Function Page Page Operation Starting Operation Cranking Control No Voltage LOW VoltageOverheating Fluctuating VoltageHigh Voltage Generator Frame Produces Shock When Touched Mechanical NoiseTroubleshooting Engine Limited Warranty Warranty Period Limitations KVA Distributor Information END User / Owner InformationRPM CurrentPre Start-Up Check List Start-Up Procedure Oregon Street Oshkosh WI Phone 920-239-4200 Fax California Proposition 65 Warning Oregon Street Oshkosh WI Phone 920 236-4200 Fax 920