Baldor ISO9001 manual Mechanical Noise, Generator Frame Produces Shock When Touched

Page 39

OVERHEATING (continued)

CAUSE

CHECK AND REMEDY

High room temperature.

Improve ventilation.

Insufficient circulation.

Provide cross-ventilation.

Low power factory.

Reduce inductive loads or install power factor

 

improvement capacitors.

Unbalanced load

The load on each leg should be as evenly balanced as

 

possible and should not exceed the rated current on

 

any leg.

Dry bearing.

Replace bearing.

 

MECHANICAL NOISE

CAUSE

CHECK AND REMEDY

Defective bearing.

Replace bearing.

Rotor scrubbing on stator.

Bad bearing; replace. Bent shaft, return to factory.

 

Loosen end bell, tighten; loose drive discs, tighten.

Loose laminations.

Return to factory.

Loose or misaligned coupling.

Tighten or align.

GENERATOR FRAME PRODUCES SHOCK WHEN TOUCHED

CAUSE

CHECK AND REMEDY

Static charge.

Ground generator frame.

Grounded armature or field coil.

Return to factory for repair.

Image 39
Contents Standby Permanent Mount Series Generator Forward Page Page Ż ż for Gasoline or Diesel Powered Generator Sets ż ż ż ż Ż ż for Gasoline or Diesel Powered Generator Sets ż ż ż ż Standby PERMANENT- Mount Series Generator Baldor Baldor Generator Features OptionsEngine Specifications Farm Duty 1-Phase Model DLC25Model D50 PowerPAC Farm Duty 1-Phase Model DLC50Model D60 Engine Specifications Farm Duty 1-Phase Model DLC60Model D75 Engine Data Farm Duty 1-Phase Model DLC75Model D100 Model DLC100 Farm Duty 1-PhaseModel D130 Farm Duty 1-Phase Model DLC130 Electrical Connection Information Hard Wire Load Terminal BlockConnection Information Generator Mounting Requirements Engine Cooling RequirementsStandby Permanent Mount Series Generator Engine Cooling AIR Backpressure must not exceed 20 of water column HOT Exhaust GasesPage Generator END Cooling AIR Building VentilationBuilding Ventilation Exhaust Piping Exhaust RequirementsExhaust Thimble Minimum O.D Exhaust Piping Thru Walls and RoofsDouble Thimble Roof Outlet Details Control Panel Operation Function Page Page Operation Starting Operation Cranking Control LOW Voltage No VoltageFluctuating Voltage High VoltageOverheating Mechanical Noise Generator Frame Produces Shock When TouchedTroubleshooting Engine Limited Warranty Warranty Period Limitations Current Distributor Information END User / Owner InformationRPM KVAPre Start-Up Check List Start-Up Procedure Oregon Street Oshkosh WI Phone 920-239-4200 Fax California Proposition 65 Warning Oregon Street Oshkosh WI Phone 920 236-4200 Fax 920