The Hour Meter accumulates and displays the total running time of the generator set.

E.VOLTAGE ADJUST - The rheostat allows the user to “fine tune” the generator set’s voltage output. It is normally used to adjust output voltage after switching the output of the generator set to a different voltage.

F.METERS - These meters monitor and display the current operating parameters of the generator set. The Voltmeter monitors and displays the current operating AC output of the generator set.

The Hertz Meter monitors and displays the current operating frequency of the generator set.

The Ammeter monitors and displays the amount of current that is being delivered by the generator set. This meter works in conjunction with the Ammeter Switch (Item G) in determining which output leg to monitor.

G.AMMETER SWITCH - The switch allows the user to switch between L1, L2 and L3 to monitor the current in each output leg to monitor.

H.PANEL LIGHT - By turning on the panel light switch, the panel lights ( Not pictured on diagram) will be energized and will illuminate the control panel. They will also illuminate

when a fault condition or a warning condition develops.

I - SYSTEM FAULT INDICATORS - These lights will come on when a fault condition or a warning condition develops.

The “Low Oil Pressure” light will come on when the engine’s oil pressure drops below 15 PSI. This condition will trigger a fault shut-down and the unit will stop.

The “Over-crank” light will come on when the engine has failed to start after four attempted crank cycles. Each crank cycle consists of a 12 second time period followed by a 12 second rest time period.

The “Over-speed” light will come on when the engine’s operating speed rises above it’s normal operating parameters. This condition will trigger a fault shut-down and the engine will stop.

High Temperature light will come on when the engine’s operating temperature exceeds the safety set- point.

Image 32
Contents Standby Permanent Mount Series Generator Forward Page Page Ż ż for Gasoline or Diesel Powered Generator Sets ż ż ż ż Ż ż for Gasoline or Diesel Powered Generator Sets ż ż ż ż Standby PERMANENT- Mount Series Generator Baldor Generator Features Options BaldorFarm Duty 1-Phase Model DLC25 Engine SpecificationsModel D50 Farm Duty 1-Phase Model DLC50 PowerPACModel D60 Farm Duty 1-Phase Model DLC60 Engine SpecificationsModel D75 Farm Duty 1-Phase Model DLC75 Engine DataModel D100 Farm Duty 1-Phase Model DLC100Model D130 Farm Duty 1-Phase Model DLC130 Hard Wire Load Terminal Block Electrical Connection InformationConnection Information Standby Permanent Mount Series Generator Generator Mounting RequirementsEngine Cooling Requirements Engine Cooling AIR HOT Exhaust Gases Backpressure must not exceed 20 of water columnPage Building Ventilation Generator END Cooling AIRBuilding Ventilation Exhaust Requirements Exhaust PipingExhaust Piping Thru Walls and Roofs Exhaust Thimble Minimum O.DDouble Thimble Roof Outlet Details Control Panel Operation Function Page Page Operation Starting Operation Cranking Control No Voltage LOW VoltageOverheating Fluctuating VoltageHigh Voltage Generator Frame Produces Shock When Touched Mechanical NoiseTroubleshooting Engine Limited Warranty Warranty Period Limitations Distributor Information END User / Owner Information RPMKVA CurrentPre Start-Up Check List Start-Up Procedure Oregon Street Oshkosh WI Phone 920-239-4200 Fax California Proposition 65 Warning Oregon Street Oshkosh WI Phone 920 236-4200 Fax 920