Xantrex Technology ACCB-L-L1 manual Dual Inverters 240 Vac Loads, AC Input/Output Off

Page 56

Operation

AC Input/Output Off

No power to the load or inverter (Figure 3-4).

In this configuration, power from both the external sources of AC and the inverter is removed from the loads. This allows the inverter that is connected to the AC Bypass breaker to be removed for service.

AC Input from Grid or Gen

ON

ON

60

60

OFF

OFF

 

INVERTER

INVERTER

 

 

Bypass 1

DISCONNECT 1

 

 

on to bypass

on for normaloperation

 

 

 

 

 

BOTH OFF TO DISCONNECT AC OUTPUT

Both external AC source and the Inverter are OFF

AC Output to Loads

Figure 3-4AC Output OFF

Dual Inverters: 240 Vac Loads

WARNING: Fire Hazard

In a series-stacked, inverter installation (120/240 Vac) with an AC Bypass switch for each inverter, both AC Bypass switches must be in the same position.

If the AC Bypass switches are not in the same position, the resulting AC output of the two AC Bypass switches may not be 180° out-of-phase from each other. This can result in excess current on the neutral wire creating a potential fire hazard.

This can also result in less than 240 Vac output. Loads requiring 240 Vac will not run.

Some 240 Vac equipment may also be damaged if one AC “leg” is lost.

3–4

973-0031-01-01 Rev A

Image 56
Contents Sine Wave Plus Long AC Conduit Box Owner’s Guide Page Sine Wave Plus Long AC Conduit Box Date and Revision Purpose ScopeAudience OrganizationRelated Information Conventions UsedAbbreviations and Acronyms Important Safety Instructions Explosive gas precautions CertificationsContents Operation Figures Page Tables Xii Introduction Introduction 1The Sine Wave Plus ACCB-L BasicACCB-L-L1 Specifications ACCB-L ACCB-L-L13ACCB-L Dimensions not to scale AC Bypass Switch Assembly For more information see , Operation in this guideBlockoff Plates 5Blockoff PlatesPage Installation Code Compliance Preparing for the InstallationInstallation Tools and Materials On-Grid Configurations Configuration PlanningOff-Grid Configurations Location Pre-InstallationService Planning Ventilation Requirements 12 305 mm Required Shock Hazard Warning Label3Cover Removal and Replacement Removing and Replacing the CoverInstalling or Removing the Blockoff Plates 4The Blockoff Plate on the Long AC Conduit BoxKnockout Preparation 5SW Plus Inverter, AC Side Showing Knockout Location6Knockouts Locations Installing Additional Breakers 7Installing Additional Breakers on the DIN RailMounting Mounting on the Xantrex Back Plate XBP9Installing the ACCB-L on the Backplate Mounting on Plywood To mount the Long AC Conduit Box on plywoodWiring General Wire Sizes and Disconnect Requirements 1Torque Values for Wiring11ACCB-L Approved Internal Components 12ACCB-L-L1 Internal Components Factory installed Installation Wiring for Off-Grid Applications Single Inverter Configurations 120 VacInstallation Step-down Configurations 240 Vac to 120 Vac Installation Step-up Configuration Deep Well Pump 120 Vac to 240 Vac Dual Inverter Configurations 120 Vac and 240 Vac Wiring for On-Grid Applications 20Wiring an On-grid Application Using a Single InverterInstallation Step-up Configurations Utility Backup 120 Vac to 240 Vac Dual Inverter Configurations 120 Vac and 240 Vac Additional Accessory Wiring 24Accessory Wiring for Single-Inverter Configurations25Accessory Wiring for Dual-Inverter Configurations Operation AC Bypass Switch Operating the AC Bypass SwitchNormal Operation Bypass OperationDual Inverters 240 Vac Loads AC Input/Output OffWarranty and Return Information WarrantyExclusions DisclaimerProduct Out of Warranty Service Return Material Authorization PolicyReturn Procedure Information About Your System Serial Number Purchased From Purchase DateIndex IX-2 Rev a Page Xantrex Technology Inc